11
GB
D
F
E
I
NL
P
GR
RU
TR
CZ
SV
HG
PO
Total operating current of
the Indoor unit
Minimum wire thickness (mm
2
)
Ground-fault interrupter *
1
Local switch (A)
Breaker for wiring (A)
(Non-fuse breaker)
Main cable
Branch
Ground
Capacity
Fuse
F0 = 16 A or less *
2
1.5
1.5
1.5
20 A current sensitivity *
3
16
16
20
F0 = 25 A or less *
2
2.5
2.5
2.5
30 A current sensitivity *
3
25
25
30
F0 = 32 A or less *
2
4.0
4.0
4.0
40 A current sensitivity *
3
32
32
40
Apply to IEC61000-3-3 about Max. Permissive System Impedance.
*1 The Ground-fault interrupter should support Inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units
✕
1.2
Indoor unit
V1
V2
Type1
PLFY-VBM, PMFY-VBM, PEFY-VMS, PCFY-VKM, PKFY-VHM,
PKFY-VKM, PFFY-VKM, PFFY-VLRMM
18.6
2.4
Type2
PEFY-VMA
38
1.6
Type3
PEFY-VMHS
13.8
4.8
Others
Other indoor unit
0
0
C : Multiple of tripping current at tripping time 0.01s
Please pick up “C” from the tripping characteristic of the breaker.
<Example of “F2” calculation>
F2 = 18.6
✕
4/8 + 38
✕
1/8
= 14.05
16 A brea ker (Tripping current = 8
✕
16 A at 0.01s)
G1
Current sensitivity
Wire thickness
V3
30 or less
30 mA 0.1 sec or less
1.5 mm
2
48
100 or less
100 mA 0.1 sec or less
2.5 mm
2
56
4.0 mm
2
66
Warning:
20
C
10
8
6
4
3
2
1
0.01
0.1
1
10
60
600
6000
SAMPLE
Tr
ip
pi
ng
Ti
m
e
[s
]
Rated Tripping current (x)
Sample chart
G1 = (V2
✕
Quantity of Type1) + (V2
✕
Quantity of Type2) + (V2
✕
Quantity of Type3) + (V2
✕
Quantity of Others) + (V3
✕
Wire length [km])
*3 Current sensitivity is calculated using the following formula.
F2 = {V1
✕
(Quantity of Type1)/C} + {V1
✕
(Quantity of Type2)/C} + {V1
✕
(Quantity of Type3)/C} + {V1
✕
(Quantity of Others)/C}
*Condition PEFY-VMS
✕
4 + PEFY-VMA
✕
1, C = 8 (refer to right sample chart)
•
•
Caution:
•
•
•
•
Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly,
heating or fire may result.
Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger
of electric shock.
Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
This device is intended for the connection to a power supply system with a maximum permissible system impedance (Refer to IEC61000-3-3.) at the
interface point (power service box) of the user's supply.
The user must ensure that this device is connected only to a power supply system which fulfils the requirement above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.
Notes:
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too large capacity may cause a risk of
malfunction or fire.
•
Backup operation
Even when the electrical work has not been completed, the fan and the drain pump can be operated by connecting the jumper (SWE) on the control board to the ON-side
and energizing the terminal block.
SWE
SWE
OFF
ON
OFF
ON
Reconnect the SWE on the control board to the OFF-side upon completion of all work.
10.2. Connecting remote controller, indoor
and outdoor transmission cables
•
Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The “S” on indoor unit TB5 is a shielding wire connection. For specifications
about the connecting cables, refer to the outdoor unit installation manual.
•
Install a remote controller following the manual supplied with the remote con-
troller.
•
Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)
•
Connect the “M1” and “M2” on indoor unit TB5 to a ME remote controller.
(Non-polarized 2-wire)
[Fig. 10.2.1]
(P.4) MA Remote controller
[Fig. 10.2.2]
(P.4) ME Remote controller
A
Terminal block for indoor transmission cable
B
Terminal block for outdoor transmission cable
C
Remote controller
•
DC 9 to 13 V between 1 and 2 (MA remote controller)
•
DC 24 to 30 V between M1 and M2 (ME remote controller)
[Fig. 10.2.3]
(P.4) MA Remote controller
[Fig. 10.2.4]
(P.4) ME Remote controller
A
Non-polarized
B
Upper level (TB15)
C
Remote Controller
D
Lower level (TB5)
•
The MA remote controller and the ME remote controller cannot be used at the
same time or interchangeably.
WT04891X03_en.p65
2012.7.20, 5:30 PM
11