[2-8 Restrictions on Refrigerant Pipes ]
20
-
chapter 2
BS_02_C
2
Rest
rict
io
ns
2-8-2
Restrictions on Refrigerant Pipe Size
(1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdoor unit pipe
size)
*1 Use ø12.7 [1/2"] pipes if the piping length exceeds 90 m [295 ft].
(2) Size of the refrigerant pipe between the first branch and the indoor unit (indoor unit pipe size)
Outdoor unit set name
(total capacity)
Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch]
250 model
ø9.52 [3/8"] *1
ø22.2 [7/8"]
model
Pipe diameter (mm) [inch]
250 model
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø22.2 [7/8"]
500 model
Liquid pipe
ø15.88 [5/8"]
Gas pipe
ø28.58 [1-1/8"]