[8-9 Troubleshooting Inverter Problems ]
32
-
chapter 8
BS_08_C
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
8-9-9
Checking the Fan Board for Damage at No Load
8-9-10
Checking the Fan Board for Damage with Load
Items to be checked
Phenomena
Remedy
(1)
Stop the unit.
Turn off the breaker.
*Be sure to turn off the power.
1)
An error other than the current sen-
sor error (5305, 5306 Detail code
135) is detected within 30 seconds
from the startup of operation.
Replace the fan board.
(2)
To allow for the disconnection
of output wiring from the fan
motor, disconnect connector
RYFAN1.
2)
Inter-wire voltage imbalance of 5 V or
above
Replace the fan board.
(3)
Set SW7-2 on the control
board to ON.
3)
No inter-wire voltage imbalance ex-
ists. A current sensor error (Detail
code 135) is detected 30 seconds af-
ter the startup of operation, and the
operation stops.
Normal
*When done checking, reconnect all
connectors as they were. Unless
they are properly reconnected, cur-
rent sensor fault will not be resolved.
(4)
Turn on the breaker.
(5)
Operate the unit
Items to be checked
Phenomena
Remedy
(1)
Turn off breaker.
1)
The operation stops within 20 seconds
of startup and a step-out error or an
overcurrent error occurs.
Check code: 4255, 4256
Detail code: 101, 106, 107, 137
Check for fan motor lock.
→
If locked, change for fan motor.
If the same error is still present
after changing fan motor, change
Fan board.
→
If not locked, refer to 3) & 4).
(2)
Turn on breaker.
2)
Motor synchronization loss or electrical
current overload during operation
Check code: 4255, 4256
Detail code: 101, 106, 107, 137
a. Check for gusts or windy conditions.
b. Go to [8-9-8 Checking the Fan
Board Error Detection Circuit at No
Load]if not windy.
c. After checking [8-9-9 Checking the
Fan Board for Damage at No
Load], and there is no problem,
change Fan board.
d. If replacing Fan board doesn't re-
solve issue, change fan motor.
(3)
Operate unit.
3)
Sensor error during operation
Check code: 5305, 5306
Detail code: 135, 136
a. Check for disconnection of fan in-
verter output wiring and for broken
wiring.
b. If the error is not associated with any
of the items above, replace the fan
board.
c. Change fan motor if Fan board
change doesn't resolve issue.
4)
Voltage overload error
Check code: 4225, 4226
Detail code: 109
a. Check for gusts or windy conditions.
b. Change Fan board if it is not windy.
5)
Load short circuit
Check code: 4255, 4256.
Detail code: 105
a. Check [8-9-7 Checking the Fan Mo-
tor for Ground Fault and Coil Resis-
tance Problems] and [8-9-8
Checking the Fan Board Error De-
tection Circuit at No Load]. If no
problem, then check wiring forshort
circuit.
b. If there is no problem with item a.
above, change fan motor.
c. If same error after motor change,
change Fan board.
6)
After RPM has stabilized, voltage unbal-
ance of 5%, or 5V.
a. If voltage is unbalanced, go to [8-9-
8 Checking the Fan Board Error
Detection Circuit at No Load]
b. After checking [8-9-9 Checking the
Fan Board for Damage at No
Load], and there is no problem,
change Fan board.
c. If replacing Fan board doesn't re-
solve issue, change fan motor.
0000004498.BOOK 32 ページ 2018年1月5日 金曜日 午前10時38分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...