[5-1 Dipswitch Functions and Factory Settings ]
BS_05_C
chapter 5 -
5
5
Cont
rol
(3) Fan board
Only the addresses are preset before shipment (All other switches are set to OFF.) Unless otherwise specified, leave the
switch to OFF where indicated by "-," which may be set to OFF for a reason.
To set the address, only set SW1-3 to ON (= address 5).
Leave SW1-1 to OFF during normal operation. Setting this switch to ON will disable the error detection function and may result
in equipment damage.
Switch
Function
Function according to switch
setting
Switch setting timing
OFF
ON
SW1
1
Enabling/Disabling no-load operation
No-load operation will continue for ap-
proximately 30 seconds, and then the
unit will come to an abnormal stop. For
details, refer to the following page(s). [8-
9-9 Checking the Fan Board for Damage
at No Load]
No-load oper-
ation disabled
No-load oper-
ation enabled
Anytime after power on
2
- -
-
-
3
Address setting. See the notes below.
0
5
Before power on
4
- -
-
-
0000004495.BOOK 5 ページ 2017年12月26日 火曜日 午前11時44分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...