Error Code Definitions and Solutions: Codes [3000 - 3999]
7-5-1
Error Code [3511]
1. Error code definition
Refrigerant overcooling
2. Error definition and error detection method
1) If the condition "THHS
≤
A
*1
°C remains true for continuous 6 minutes and 30 seconds" is met (for the first time) during oper-
ation, the outdoor unit will stop, go into the 20-second restart delay mode, and then automatically resume operation after 20
seconds have passed.
2) If the condition "THHS
≤
A
*1
°C remains true for continuous 6 minutes and 30 seconds" is met again (for the second time)
within 30 minutes of the first stoppage of the outdoor unit explained above, the outdoor unit will stop, go into the 20-second
restart delay mode, and then automatically resume operation after 20 seconds have passed.
3) If the condition "THHS
≤
A
*1
°C remains true for continuous 6 minutes and 30 seconds" is met again (for the third time) within
30 minutes of the second stoppage of the outdoor unit explained above and before the condition "THHS > A
*1
°C remains true
for continuous 2 minutes" has been met, the unit will come to an abnormal stop, and this error will be indicated as "3511."
4) If the condition "THHS
≤
A
*1
°C remains true for continuous 6 minutes and 30 seconds" is met (regardless of the first or second
time) after 30 minutes of the first occurrence or after the condition "THHS > A
*1
°C remains true for continuous 2 minutes" has
been met, it is considered as the first occurrence, and the unit will follow the same behavior as the one described in item 1)
above.
5) For 30 minutes after the stoppage of the outdoor unit, or the period up to the time when the condition "THHS > A
*1
°C remains
true for continuous 2 minutes" has been met is considered as a preliminary error, and this state will be indicated on the LED.
*1 During cooling: A = Outside temperature TH7
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Outdoor unit LEV9 malfunction
Check the operation of unit in the Cooing mode.
LEV9
Refer to [8-8 Troubleshooting LEV Problems].
(2)
THHS failure
1)
Check the IGBT on the INV board for proper mounting.
2)
Check the THHS sensor reading on the LED.
→
Replace the INV board if the THHS value is abnormal.
(3)
Thermistor failure (TH7)
Resistance value of the thermistor
(4)
Low-pressure sensor fault
Refer to [8-5 Pressure Sensor Circuit Configuration and
Troubleshooting Pressure Sensor Problems]
0000004497.BOOK 11 ページ 2017年12月26日 火曜日 午前11時46分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...