"HO" and "PLEASE WAIT" Do Not Go Off the Screen.
1. Phenomena
"HO" or "PLEASE WAIT" display on the remote controller does not disappear, and no operation is performed even if the button
is pressed. ("HO" or "PLEASE WAIT" display will normally turn off 5 minutes later after the power on.)
2. Cause
1) The power for the M-NET transmission line is not supplied from the outdoor unit. For details, refer to the following page(s).
[8-10-2 Troubleshooting Problems with Outdoor Unit Transmission Power Supply Circuit]
2) Short-circuited transmission line
3) Incorrect wiring of the M-NET transmission line on the outdoor unit.
Disconnected wire for the MA remote controller or disconnected line to the terminal block.
The indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7).
The male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector
(CN40).
In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect-
ed to the female power supply switch connector (CN40) on the outdoor unit
4) Disconnected M-NET transmission line on the indoor unit.
5) Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or
disconnected connector.
6) Incorrect wiring for the MA remote controller
Short-circuited wire for the MA remote controller
Disconnected wire for the MA remote controller (No.2) and disconnected line to the terminal block.
Reversed daisy-chain connection between groups
Incorrect wiring for the MA remote controller to the terminal block for transmission line connection (TB5) on the indoor unit
The M-NET transmission line is connected incorrectly to the terminal block (TB13) for the MA remote controller.
7) The sub/main setting of the MA remote controller is set to sub.
8) 2 or more main MA remote controllers are connected.
9) Indoor unit board failure (MA remote controller communication circuit)
10) Remote controller failure
11) Outdoor unit failure (Refer to the following page(s).[8-13 Troubleshooting Problems Using the LED Status Indicators on the
Outdoor Unit])
12) The outdoor unit address is set to an address other than "indoor unit address plus 50."
13) The indoor unit address is set to a number 51 or highe
3. Check method and remedy
When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.
YES
YES
YES
NO
YES
YES
NO
NO
Check the self-diagnosis LED
Error found?
Error found?
Replace the M-NET remote
controller with the MA
remote controller
Check for 5), 6), 12) and 13).
17 - 30V?
Same symptom for all units in a
system with one outdoor unit?
Check 1).
Check
2) and 3).
Check 4).
Correct
the error.
Correct
the error.
Measure voltages of the
terminal block for transmission
line (TB5) on the indoor unit.
Is the error code 7102
displayed?
Indoor unit board or
MA remote controller failure
NO
0000004498.BOOK 3 ページ 2018年1月5日 金曜日 午前10時38分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...