[5-2 Outdoor Unit Control ]
BS_05_C
chapter 5 -
19
5
Cont
rol
(5) Running/Stopping the Units on Rotation
Indoor units whose SW9 (Normal/Local switching switch) is set to "Local" will not be able to accept the Run/Stop signal from
the control unit and will not operate properly. After the unit whose SW9 is set to "Local" is operated or stopped from the MA
remote controller, the operation status needs to be changed back to the original status, and the SW9 setting needs to be set
back to "Normal."
If an attempt is made to Run/Stop the indoor unit whose SW9 is set to "Normal", the following types of errors may happen.
Example 1 Backup units are not rotated when the system rotation timer has reached 480 hours.
Example 2 The backup unit does not go into operation when a unit in the group detects an error.
These symptoms can be solved by bringing the stopped unit into operation. By doing so, although all the units will temporarily
operate, the rotation function will remain effective.
(6) When an Error Occurs
If an error is detected by a unit or a communication failure between the systems in the group while the rotation function is
enabled, the units will perform the actions as described in Table 1, and the rotation control will be temporarily stopped.
When the starting conditions are met, this function will be resumed, and the rotation sequence and the system rotation timer
count effective at the time of error will be kept.
Table.1 Operation of Units during an Error
(7) Rotation Function Test Run Mode
Proper operation of the rotation function can be checked in a short time using the rotation function test run mode.
Rotation function test run mode can be initiated by starting the control unit in the test run mode (via MA remote controller).
In this mode, the system rotation timer setting is reduced to approximately three minutes (from the usual 480 hours), and the
test run will automatically end when the control unit is rotated to the backup unit.
At the completion of the test run mode, the system rotation timer setting goes back to 480 hours, and this function will remain
effective.
Important Notes on Rotation Control
All the units in the system using the rotation function must be the same capacity and installed within the same area to be
cooled.
Check that the items to be cooled are not affected no matter which unit stops when designated as a backup unit.
The backup unit automatically goes into operation only when there is a problem with other units in the group. It will not auto-
matically go into operation even if the heat load increases.
The control unit cannot perform a test run while the system rotation function is performed. Disable the system rotation control
function to perform a test run.
If multiple units are grouped with an MA remote controller or an AE-200E controller, this control function will not work properly.
Rotation status
A unit in the group made an abnor-
mal stop.
Communication failure between
systems
Control unit
Backup unit
Goes into operation
Goes into operation
Regular unit
Sends a startup signal to the back-
up unit
Sends a startup signal to the back-
up unit
Other units
Backup unit
Goes into operation by receiving a
signal from the control unit
1) Goes into operation by re-
ceiving a signal from the con-
trol unit
2) Goes into operation
*1
*1. The backup unit will automatically resume its operation when periodical communication from the control unit is lost.
Regular unit
Sends its own error status to the
control unit
-
0000004495.BOOK 19 ページ 2017年12月26日 火曜日 午前11時44分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...