[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
BS_07_C
chapter 7 -
47
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-8-12
Error Code [6607] No Error Source Address
1. Error code definition
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Although the address of ME remote controller has been
changed after the group is set using ME remote control-
ler, the indoor unit is keeping the memory of the previous
address. The same symptom will appear for the registra-
tion with SC.
Delete unnecessary information of non-existing
address which some indoor units have.
Use either of the following two methods for dele-
tion.
(2)
Although the address of LOSSNAY has been changed af-
ter the interlock registration of LOSSNAY is made using
ME remote controller, the indoor unit is keeping the mem-
ory of the previous address.
1)
Address deletion by ME remote controller
Delete unnecessary address information using the
manual setting function of ME remote controller.
Refer to the ME remote controller instructions
manual for detail.
2)
Deletion of connection information of the outdoor
unit by the deleting switch
Note that the above method will delete all the
group settings set via the ME remote controller and
all the interlock settings between LOSSNAY units
and indoor units.
Procedures
1) Turn off the power source of the outdoor unit,
and wait for 5 minutes.
2) Turn on the dip switch (SW5-2) on the outdoor
unit control board.
3) Turn on the power source of the outdoor unit,
and wait for 5 minutes.
4) Turn off the power source of the outdoor unit,
and wait for 5 minutes.
5) Turn off the dip switch (SW5-2) on the outdoor
unit control board.
6) Turn on the power source of the outdoor unit.
0000004497.BOOK 47 ページ 2017年12月26日 火曜日 午前11時46分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...