[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
BS_07_C
chapter 7 -
21
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-6-13
Error Codes [4235, 4236] Detail Code 125
1. Error code definition
Heatsink overheat protection (Detail code 125) (outdoor unit)
2. Error definition and error detection method
Detection of fan INV heatsink temperature (THHS)
≥
100°C
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
7-6-14
Error Code [4230] Detail Code 126
1. Error code definition
DCL temperature fault (Detail code 126)(outdoor unit)
2. Error definition and error detection method
When DCL temperature that equals or exceeds 150
˚
C is detected (applicable to INV37YC only)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
FAN board fault
Refer to the following page(s).
[8-9-8 Checking the Fan Board Error Detection Circuit at No Load]
[8-9-9 Checking the Fan Board for Damage at No Load]
[8-9-10 Checking the Fan Board for Damage with Load]
(2)
Outdoor unit fan failure
1)
Check the outdoor unit fan for proper operation.
Check the fan motor if problems are found with the operation of the fan.
Refer to the following page(s). [8-9-7 Checking the Fan Motor for Ground Fault
and Coil Resistance Problems]
(3)
Air passage blockage
1)
Check the heatsink and the duct for blockage.
Refer to the following page(s). [8-9-16 Checking the Fan Inverter Heatsink for
Clogging]
(4)
THHS failure
1)
Check the IGBT heatsink for proper mounting.
2)
Check the THHS sensor reading on the LED.
→
Replace the INV board if the THHS value is abnormal.
Cause
Check method and remedy
(1)
Contact failure
Check the connector CNTH on the INV board for proper connection.
(2)
DCL temperature sen-
sor fault
Disconnect the connector (CNTH), and measure the resistance of the DCL temper-
ature sensor. Replace the DCL temperature sensor if the value is abnormal. Refer
to [3-4 Functions of the Major Components of Outdoor Unit].
(3)
INV board failure
Replace the INV board if the problem persists after the operation is resumed.
0000004497.BOOK 21 ページ 2017年12月26日 火曜日 午前11時46分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...