[8-2 Refrigerant Control Problems ]
6
-
chapter 8
BS_08_C
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
Cause
Check method and remedy
3.
RPM error of the outdoor unit FAN
Refer to the following page(s).
[8-7 Troubleshooting Outdoor Unit Fan Problems]
[7-3-3 Error Code [1302] (during operation)]
Motor failure or board failure, or airflow rate de-
crease due to clogging of the heat exchanger
The fan is not properly controlled as the outdoor
temperature cannot be precisely detected by the
temperature sensor.
The fan is not properly controlled as the pressure
cannot be precisely detected by the pressure sen-
sor.
4.
Long piping length
The cooling capacity varies greatly depending on the
pressure loss. (When the pressure loss is large, the
cooling capacity drops.)
Check the piping length to determine if it is contrib-
uting to performance loss.
Piping pressure loss can be estimated from the
temperature difference between the indoor unit
heat exchanger outlet temperature and the satura-
tion temperature (Te) of 63LS.
→
Correct the piping.
5.
Piping size is not proper (thin)
6.
Insufficient refrigerant amount
Protection works and compressor frequency does
not rise due to high discharge temperature.
Refer to item 1 (Compressor frequency does not
rise sufficiently.) on the previous page.
Refer to the following page(s). [6-3 Evaluating and
Adjusting Refrigerant Charge]
7.
Clogging by foreign object
Check the temperature difference between in front
of and behind the place where the foreign object is
clogging the pipe (upstream side and downstream
side). When the temperature drops significantly, the
foreign object may clog the pipe.
→
Remove the foreign object inside the pipe.
8.
The indoor unit inlet temperature is excessively.
(Less than 15°C [59°F] WB)
Check the inlet air temperature and for short cy-
cling. Change the environment where the indoor
unit is used.
9.
Compressor failure
The amount of circulating refrigerant decreases due
to refrigerant leak in the compressor.
Check the discharge temperature to determine if
the refrigerant leaks, as it rises if there is a leak.
10.
LEV1 malfunction
Sufficient liquid refrigerant is not be supplied to the
indoor unit as sufficient sub cool cannot be secured
due to LEV1 malfunction.
Refer to the following page(s). [8-8 Troubleshooting
LEV Problems]
It most likely happens when there is little difference
or no difference between TH3 and TH6.
11.
TH3, TH6 and 63HS1 sensor failure or damaged wir-
ing
LEV1 is not controlled normally.
Check the thermistor.
Check wiring.
12.
LEV2 actuation failure
A drop in the low pressure that is caused either by a
blockage of liquid pipe or by a pressure loss and the
resultant slowing of refrigerant flow causes a tenden-
cy for the discharge temperature to rise.
Refer to the following page(s).[8-8 Troubleshooting
LEV Problems]
13.
LEV9 malfunction
Not enough refrigerant is provided to the indoor or
outdoor unit due to high-low pressure bypass that re-
sults from the malfunction of LEV9.
Refer to the following page(s). [8-8 Troubleshooting
LEV Problems]
0000004498.BOOK 6 ページ 2018年1月5日 金曜日 午前10時38分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...