[8-9 Troubleshooting Inverter Problems ]
BS_08_C
chapter 8 -
31
8 Troub
le
sho
o
ting Bas
e
d on Ob
ser
ved
Sy
mp
toms
8-9-6
Checking the Converter for Damage during Compressor Operation
8-9-7
Checking the Fan Motor for Ground Fault and Coil Resistance Problems
8-9-8
Checking the Fan Board Error Detection Circuit at No Load
Items to be checked
Phenomena
Remedy
(1)
Operate the outdoor unit.
1)
BUS voltage does not boost (does
not change) BUS voltage does not
boost to approximately between
650 and 750 VDC, or the following
errors are detected.
Error code : 4220
Detail code : 123
Replace the inverter board.
(2)
Check the BUS voltage after the
converter circuit went into oper-
ation and the BUS voltage has
boost.
*The voltage generally boost at
or above 80 rps, depending on
the power source voltage.
2)
An overcurrent error occurs after
converter circuit goes into opera-
tion.
Error code : 4250
Detail code : 121,122
a.If the problem persists after startup, re-
place the inverter board.
b.If the problem persists after replacing
the inverter board, replace the DCL.
3)
An overvoltage error occurs after
converter circuit goes into opera-
tion.
Error code : 4220
Detail code : 109,110,112
a.If the problem persists after startup, re-
place the inverter board.
b.If the problem persists after replacing
the inverter board, replace the DCL.
4)
No problems were found with items
1) through 3).
Normal
Items to be checked
Phenomena
Remedy
Remove fan motor winding. Check
insulation resistance and coil resis-
tance.
1)
Fan motor insulation failure.
If < 1 M
Ω
, Defect.
Change fan motor.
2)
Fan motor wire failure.
Target coil resistance: Approx. 10
Ω
.
(Changes with temperature)
Change fan motor.
Items to be checked
Phenomena
Remedy
(1)
Stop the unit.
Turn off the breaker.
*Be sure to turn off the power.
1)
An error other than current sensor er-
ror (5305, 5306: Detail code 135) is
detected during operation.
Replace the fan board.
(2)
Disconnect the output wiring
to the fan motor.
Disconnect connector
RYFAN1.
2)
Current sensor fault
Error code: 5305, 5306
Detail code: 135
Normal
*When done checking, reconnect all
connectors as they were. Unless
they are properly reconnected, cur-
rent sensor fault will not be resolved.
(3)
Turn on the breaker.
(4)
Operate the unit.
0000004498.BOOK 31 ページ 2018年1月5日 金曜日 午前10時38分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...