[5-2 Outdoor Unit Control ]
16
-
chapter 5
BS_05_C
5
Cont
rol
5-2-16
Control of IH energization without the compressor in operation
IH is used to heat the compressor motor on the stopped outdoor unit to make liquid refrigerant in the compressor evaporate
or to keep liquid refrigerant from flooding the compressor.
Initial power on after power is turned on: Stays on for 12 hours, and then transitions to the operation that is performed while
the compressor is stopped
When the compressor is stopped: Stays on for 30 minutes after the compressor stopped, and then repeats the on-off cycle
at 30-minute intervals
Lit LED1 on the INV board indicates that the INV board is energized by an IH.
5-2-17
Capacity Control between Outdoor Units (when two refrigerant circuits are
connected)
The following two capacity control methods between indoor units are available.
Control to make only one of the outdoor units (which has the smaller address) operate and keep running during low-load hours
at startup.
Control to make one of the outdoor units stop, and the other outdoor unit operate when the load becomes low during normal
operation. After a certain period of time has passed since only one of the outdoor units started operation, the unit in operation
stops, and the other outdoor unit starts operation automatically.
(1) Starting Conditions
Air conditioning load that is calculated based on the return air temperature is 50% or above.
Operation frequencies of both indoor and outdoor units remain near the minimum level three minutes after start-up.
(2) Stopping Conditions
When operation frequency of the running unit rises up near the maximum capacity.
When it is determined that the load is over 50%, using suction temperature as a reference.
When compressor stops while running only one unit.
5-2-18
Dehumidification Priority Control
The dehumidification priority control is the control to increase the amount of dehumidification by increasing the frequency of
the compressor when the external signal (dehumidification command) is received during cooling operation.
During dehumidification priority control, the room temperature may drop below the preset temperature set during normal op-
eration.
Under this control, the set temperature will be compulsory at the minimum value.
(Under discharge temperature control:14°C [57°F]. Under suction temperature conrol:19°C [66°F])
The temperature nor the humidity can be controlled simultaneously as the reheat function is not available.
0000004495.BOOK 16 ページ 2017年12月26日 火曜日 午前11時44分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...