[2-7 Example System with an MA Remote Controller ]
BS_02_C
14
-
chapter 2
2
Rest
rict
io
ns
(4) Wiring method
1) Indoor/outdoor transmission line
Connect M1, M2 terminals of the indoor/outdoor trans-
mission line terminal block (TB3) on the outdoor unit
(OC) and A1, B1 terminals of the indoor/outdoor terminal
block (TB5-1) on the indoor unit (IC). (Non-polarized 2-
core cable)
Only use shielded cables.
Shielded cable connection
Connect the earth terminal of the OC and S terminal of
the IC terminal block (TB5-1).
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block
for transmission line for centralized control (TB7) on
each outdoor unit (OC). Disconnect the male connector
on the controller board from the female power supply
switch connector (CN41), and connect it to the female
power supply switch connector (CN40) on only one of the
outdoor units.
Only use shielded cables.
Shielded cable connection
To ground the shielded cable, daisy-chain the S-termi-
nals on the terminal block (TB7) on each of the outdoor
units. Connect the S (shielded) terminal on the terminal
block (TB7) on the outdoor unit whose male connector
on CN41 was disconnected and connected to CN40 to
the earth terminal( ) on the electric box.
3) Switch setting
Address setting is required as follows.
(5) Address setting method
Procedures
Unit or controller
Address
setting range
Setting method
Notes
Factory
setting
1
Indoor
unit
Main unit
IC
01 to 50
Assign a sequential odd number
starting with "01" to the upper in-
door controller.
00
Sub unit
IC
01 to 50
Assign sequential numbers start-
ing with the address of the main
unit in the same group. (Main
unit a1)
2
Outdoor unit
OC
51 to 100
Add 50 to the address assigned
to the indoor unit connected to
the system with one outdoor unit.
00
3
MA
remote
controller
Main
remote
controller
MA
No settings
required.
-
Main
Sub
remote
controller
MA
Sub
remote
controller
Settings to be made with the sub/
main switch
0000004492.BOOK 14 ページ 2018年1月5日 金曜日 午前10時12分
Содержание PFD-P250VM-E
Страница 1: ...AIR CONDITIONER 2017 Service Handbook PUHY P250YNW A PUHY P500YSNW A PFD P250VM E PFD P500VM E Model ...
Страница 11: ...GB_BS_01_C 0000004491 BOOK 2 ページ 2017年12月26日 火曜日 午後1時10分 ...
Страница 27: ...GB_BS_02_C 0000004492 BOOK 2 ページ 2018年1月5日 金曜日 午前10時12分 ...
Страница 49: ...GB_BS_03_C 0000004493 BOOK 2 ページ 2018年1月5日 金曜日 午前9時11分 ...
Страница 71: ...GB_BS_04_C 0000004494 BOOK 2 ページ 2017年12月26日 火曜日 午前11時43分 ...
Страница 89: ...GB_BS_05_C 0000004495 BOOK 2 ページ 2017年12月26日 火曜日 午前11時44分 ...
Страница 117: ...GB_BS_06_C 0000004496 BOOK 2 ページ 2017年12月26日 火曜日 午前11時45分 ...
Страница 281: ...GB_BS_09_A1 0000004538 BOOK 2 ページ 2017年12月25日 月曜日 午後7時48分 ...
Страница 299: ...GB_BS_10_C 0000004550 BOOK 2 ページ 2017年12月26日 火曜日 午後12時1分 ...