CC-Link IE Field Network (FR-A800-GF)
Parameters
5 - 754
5.21.4 Details
of
remote register
The following device numbers are those for station 1.
For stations 2 and later, the device numbers are different. (Refer to the master module manual for cor-
respondence between the device numbers and station number.)
Remote register (from the master module to the inverter)
Device No.
Signal
Description
RWw0
Set frequency
앫
Specify the set frequency or rotations per minute (machine speed). At this time,
whether to write to RAM or EEPROM is decided with the RY21 and RY22 settings.
After setting the set frequency in this register, set "1" in RY21 or RY22 to write the
frequency. After writing of frequency is completed, "1" is set in RX21 or RX22 in
response to the input command.
앫
The setting range is 0 to 590.00 Hz (0.01 Hz increments). Write "59000" when
setting 590.00 Hz.
Torque command value
Specify the torque command value / torque limit value. Set Pr. 804 "Torque command
source selection" = "1, 3, 5, or 6" to activate this signal under Real sensorless vector
control, vector control, and PM sensorless vector control. The value is written to the
inverter either by RY23 or RY24. Pr. 805 "Torque command value (RAM)" and Pr. 806
"Torque command value (RAM, EEPROM)" are updated as well. The setting range and
setting increments depend on the Pr.804 setting. (Refer to page 5-759).
Torque limit value
RWw4
PID set point
Set the PID set point.
Setting range: "0 to 100.00%"
앫
Input a value 100 times greater than
the value to be set.
For example, input "10000" when
setting 100.00%.
앫
Refer to page 5-543 for details of PID
control.
RWw5
PID measured value
Set the PID measured value.
Setting range: "0 to 100.00%"
RWw6
Set the PID deviation.
Setting range: "-100.00% to 100.00%"
RWw10,
RWw12,
RWw14,
RWw16,
RWw18,
RWw1A
Link parameter extended setting/
Instruction code
Set an instruction code (refer to page 5-757) for an operation such as operation mode
switching, parameter read/write, alarm reference, and alarm clear in the lower eight
bits. The instructions are executed in the following order by setting "1" in RY25 after
completing the register setting: RWw10, 12, 14, 16, 18, then 1A. After completing the
execution up to RWw1A, "1" is set in RX25. Set HFFFF to disable an instruction by
RWw10 to 1A. Set the link parameter extended setting in the upper eight bits.
Example:
When reading Pr.160, instruction code is H0200.
RWw11,
RWw13,
RWw15,
RWw17,
RWw19,
RWw1B
Write data
Set the data specified by the instruction code of RWw10, 12, 14, 16, 18 and 1A. (when
required) RWw10 and 11, 12 and 13, 14 and 15, 16 and 17, 18 and 19, and 1A and 1B
correspond each other.
Set "1" in RY25 after setting the instruction codes (RWw10, 12, 14, 16, 18 and 1A) and
the corresponding register. Set "0" when the write code is not required.
RWw21
Set the number of previous faults you want to be able to read in the faults history.
Up to 8 previous faults can be read.
Last two digits: H00 (most recent fault) to H07 (8th most recent fault).
Set H08 to HFF to make the faults history No. to "0."
RWw26
Monitor code 1
Set the monitor code to be monitored. By setting "1" in RY20 after setting, the
specified monitored data is stored in RWr26 to RWr2F.
If a monitor code out of the setting range is set, no item is monitored (the monitor
value is fixed to 0).
The monitor codes are the same as those of the RS-485 communication dedicated
monitor. (Refer to page 5-344.)
When the remote registers RWw26 to 2F are used for monitoring, H01 (output
frequency) and H05 (set frequency) always indicate the frequency regardless of the
settings of Pr. 37, Pr. 144, and Pr. 811.
RWw27
Monitor code 2
RWw28
Monitor code 3
RWw29
Monitor code 4
RWw2A
RWw2B
Monitor code 6
RWw2C
RWw2D
RWw2E
RWw2F
Monitor code 10
Tab. 5-348:
Remote register (master module
inverter)
Содержание FR-A820-00046 (0.4K)
Страница 2: ......
Страница 4: ......
Страница 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Страница 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Страница 1110: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1188: ...EC Declarations of Conformity Appendix A 48 A 7 EC Declarations of Conformity A 7 1 FR A820 FR A840 FR A842 series ...
Страница 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1190: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Страница 1192: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1194: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1196: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Страница 1198: ...EC Declarations of Conformity Appendix A 58 ...
Страница 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Страница 1200: ...EC Declarations of Conformity Appendix A 60 ...
Страница 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Страница 1202: ...EC Declarations of Conformity Appendix A 62 ...
Страница 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Страница 1204: ...EC Declarations of Conformity Appendix A 64 ...
Страница 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Страница 1206: ...EC Declarations of Conformity Appendix A 66 ...
Страница 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Страница 1208: ...EC Declarations of Conformity Appendix A 68 ...
Страница 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Страница 1210: ...EC Declarations of Conformity Appendix A 70 ...
Страница 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Страница 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Страница 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Страница 1214: ...EC Declarations of Conformity Appendix A 74 ...
Страница 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Страница 1216: ...EC Declarations of Conformity Appendix A 76 A 7 3 Frequency inverters with option unit FR A8NP ...
Страница 1217: ......