Parameters
(A) Application parameters
FR-A800
5 - 579
Priority of main speed commands
●
The priority of main speed command sources when the speed command source is External is as
follows:
JOG signal > multi-speed setting signal (RL/RM/RH/REX) > pulse train input > 16bit digital input
(option FR-A8AX) > analog input (terminals 2, 4, 1)
●
The priority of main speed command sources when "3" is set to Pr. 79 "Operation mode selection"
is as follows:
Multi-speed setting signal (RL/RM/RH/REX) > frequency setting (digital setting by PU or operation
panel)
●
Even if the remote operation function is selected by Pr. 59 "Remote function selection"
≠
"0",
compensation of the remote setting frequency against the main speed is ignored. (The value is
"0".)
●
If terminal 1 is selected for the first and second PID, terminal 1 added compensation of the main
speed is invalid.
●
If terminal 2 is selected for the first and second PID, the terminal 2 override function of the main
speed is invalid.
●
If the same terminal as an external input terminal having a speed command source (external
terminal where a main speed is input) is specified as the measured value input or set point input,
the main speed is treated as "0".
●
Polarity reversible operation of the main speed is not possible.
Adjustment procedure for dancer roll position detection signal
●
When the input of terminal 4 is voltage input, 0 V and 5 V (10 V) are the lower limit position and
upper limit position, respectively. When it is current input, 4 mA and 20 mA are the lower limit
position and upper limit position, respectively. (initial value) When the potentiometer has an
output of 0 to 7 V, C7 (Pr. 905) must be calibrated at 7 V.
Switch the current/voltage input selection switch to "OFF", set "2" to Pr. 267 and set terminal 4
input to voltage input.
Input 0 V across terminals 4 and 5, and calibrate C6 (Pr. 904). (The % display that is indicated at
analog calibration is not related to the % of the feedback value.)
Input 7 V across terminals 4 and 5, and calibrate C6 (Pr. 905). (The % display that is indicated at
analog calibration is not related to the % of the feedback value.)
Set Pr. 133 to "50%".
I002711E
Fig. 5-284:
Dancer roller position detection signal adjustment
Example
To execute control at the dancer center position using a 0 to 7 V potentiometer
0%
100%
20 mA 5 V (10 V)
4 mA
0 V
Feedback value
Lower limit
position
Upper limit
position
Potentiometer, etc.
Содержание FR-A820-00046 (0.4K)
Страница 2: ......
Страница 4: ......
Страница 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Страница 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Страница 1110: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1188: ...EC Declarations of Conformity Appendix A 48 A 7 EC Declarations of Conformity A 7 1 FR A820 FR A840 FR A842 series ...
Страница 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1190: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Страница 1192: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1194: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1196: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Страница 1198: ...EC Declarations of Conformity Appendix A 58 ...
Страница 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Страница 1200: ...EC Declarations of Conformity Appendix A 60 ...
Страница 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Страница 1202: ...EC Declarations of Conformity Appendix A 62 ...
Страница 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Страница 1204: ...EC Declarations of Conformity Appendix A 64 ...
Страница 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Страница 1206: ...EC Declarations of Conformity Appendix A 66 ...
Страница 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Страница 1208: ...EC Declarations of Conformity Appendix A 68 ...
Страница 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Страница 1210: ...EC Declarations of Conformity Appendix A 70 ...
Страница 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Страница 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Страница 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Страница 1214: ...EC Declarations of Conformity Appendix A 74 ...
Страница 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Страница 1216: ...EC Declarations of Conformity Appendix A 76 A 7 3 Frequency inverters with option unit FR A8NP ...
Страница 1217: ......