(C) Motor constant parameters
Parameters
5 - 472
90
C120
Motor constant (R1)
9999
0 to 50 Ω, 9999
Tuning data
(The value measured by offline auto
tuning is automatically set.)
9999: Uses the MM-CF constant for
the IPM motor MM-CF, and the
inverter internal data for a PM motor
other than MM-CF.
92
C122
Motor constant (L1)/
d-axis inductance (Ld)
9999
93
C123
Motor constant (L2)/
q-axis inductance (Lq)
9999
859
C126
Torque current/
Rated PM motor current
9999
0 to 500 A, 9999
0 to 3600 A, 9999
706
C130
Induced voltage constant
(phi f )
9999
Set this parameter according to the
PM motor specifications.
9999
The value calculated by the motor
constant parameter setting is used.
1412
C135
Motor induced voltage
constant (phi f ) exponent
9999
0 to 2
Set the exponent n when the
induced voltage constant phi f
(Pr. 706) is multiplied by 10
n
.
9999
No exponent setting
711
C131
Motor Ld decay ratio
9999
0 to 100%, 9999
Tuning data
(The value measured by offline auto
tuning is automatically set.)
9999: Uses the MM-CF constant for
the IPM motor MM-CF, and the
inverter internal data for a PM motor
other than MM-CF.
712
C132
Motor Lq decay ratio
9999
0 to 100%, 9999
717
C182
Starting resistance tuning
compensation
9999
0 to 200%, 9999
721
C185
Starting magnetic pole
position detection pulse
width
9999
0 to 6000 μs,
10000 to 16000 μs, 9999
725
C133
Motor protection current
level
9999
100 to 500%
Set the maximum current (OCT) level
of the motor.
9999
Uses the MM-CF constant for the IPM
motor MM-CF, and 200% for a PM
motor other than MM-CF.
450
C200
Second applied motor
9999
0, 1, 3 to 6, 13 to 16, 20, 23, 24,
30, 33, 34, 40, 43, 44, 50, 53, 54,
70, 73, 74, 330, 333, 334, 8090,
8093, 8094, 9090, 9093, 9094
Set this parameter when using the
second motor.
(the same specifications as Pr. 71).
9999
The function is disabled.
453
C201
Second motor capacity
9999
Set the capacity of the second motor.
0 to 3600 kW
9999
V/F control
454
C202
Number of second motor
poles
9999
2, 4, 6, 8, 10, 12
Set the number of poles of the
second motor.
9999
V/F control
51
C203
Second electronic thermal O/
L relay
9999
0 to 500 A
Set the rated current of the second
motor.
0 to 3600 A
9999
Second electronic thermal O/L relay
disabled.
456
C204
Rated second motor voltage
200/400
0 to 1000 V
Set the rated voltage (V) of the
second motor.
457
C205
Rated second motor
frequency
9999
10 to 400 Hz
Set the rated frequency (Hz) of the
second motor.
9999
The MM-CF constant is used when
the IPM motor MM-CF is selected for
the second motor, and the inverter
internal data is used when a PM
motor other than MM-CF is selected.
Use the correct setting according to
the motor specification.
Pr.
Name
Initial
value
Setting range
Description
Содержание FR-A820-00046 (0.4K)
Страница 2: ......
Страница 4: ......
Страница 144: ...System configuration for Ethernet communication FR A800 E Installation and wiring 2 114 ...
Страница 202: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 1090: ...Check first when you have a trouble Protective functions 6 50 ...
Страница 1110: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 1188: ...EC Declarations of Conformity Appendix A 48 A 7 EC Declarations of Conformity A 7 1 FR A820 FR A840 FR A842 series ...
Страница 1189: ...Appendix EC Declarations of Conformity FR A800 A 49 ...
Страница 1190: ...EC Declarations of Conformity Appendix A 50 ...
Страница 1191: ...Appendix EC Declarations of Conformity FR A800 A 51 ...
Страница 1192: ...EC Declarations of Conformity Appendix A 52 ...
Страница 1193: ...Appendix EC Declarations of Conformity FR A800 A 53 ...
Страница 1194: ...EC Declarations of Conformity Appendix A 54 ...
Страница 1195: ...Appendix EC Declarations of Conformity FR A800 A 55 ...
Страница 1196: ...EC Declarations of Conformity Appendix A 56 ...
Страница 1197: ...Appendix EC Declarations of Conformity FR A800 A 57 ...
Страница 1198: ...EC Declarations of Conformity Appendix A 58 ...
Страница 1199: ...Appendix EC Declarations of Conformity FR A800 A 59 ...
Страница 1200: ...EC Declarations of Conformity Appendix A 60 ...
Страница 1201: ...Appendix EC Declarations of Conformity FR A800 A 61 ...
Страница 1202: ...EC Declarations of Conformity Appendix A 62 ...
Страница 1203: ...Appendix EC Declarations of Conformity FR A800 A 63 ...
Страница 1204: ...EC Declarations of Conformity Appendix A 64 ...
Страница 1205: ...Appendix EC Declarations of Conformity FR A800 A 65 ...
Страница 1206: ...EC Declarations of Conformity Appendix A 66 ...
Страница 1207: ...Appendix EC Declarations of Conformity FR A800 A 67 ...
Страница 1208: ...EC Declarations of Conformity Appendix A 68 ...
Страница 1209: ...Appendix EC Declarations of Conformity FR A800 A 69 ...
Страница 1210: ...EC Declarations of Conformity Appendix A 70 ...
Страница 1211: ...Appendix EC Declarations of Conformity FR A800 A 71 ...
Страница 1212: ...EC Declarations of Conformity Appendix A 72 A 7 2 FR A846 series ...
Страница 1213: ...Appendix EC Declarations of Conformity FR A800 A 73 ...
Страница 1214: ...EC Declarations of Conformity Appendix A 74 ...
Страница 1215: ...Appendix EC Declarations of Conformity FR A800 A 75 ...
Страница 1216: ...EC Declarations of Conformity Appendix A 76 A 7 3 Frequency inverters with option unit FR A8NP ...
Страница 1217: ......