Monitor display and monitor output signal
(3) Terminal AM response adjustment
(Pr.867)
• Using
Pr. 867
, the output voltage response of the terminal AM can be adjusted within the range 0 to 5s.
• Increasing the setting stabilizes the terminal AM output more but reduces the response level. (Setting "0" sets the
response level to 7ms)
(4) Adjustment of response level of terminal CA
(Pr.869)
• The response level of the output current of the terminal CA can be adjusted between 0 and 5s with
Pr. 869
.
• Increasing the setting stabilizes the terminal CA output more but reduces the response level. (Setting "0" sets the
response level to about 7ms.)
i
Parameters referred to
i
Pr. 37 Speed display