OCH791 _96
SW1
setting
Contents
LED1, 2
No. 12345678
1
2
3
4
5
6
7
8
220 00111011 IC6 TH23 (Gas)
−99.9–999.9 (°C)
Note: Display detected data of indoor unit thermistor
221 10111011 IC7 TH23 (Gas)
222 01111011 IC8 TH23 (Gas)
223 11111011 IC6 TH22 (liquid)
224 00000111 IC7 TH22 (liquid)
225 10000111 IC8 TH22 (liquid)
226 01000111 IC6 TH21 (intake)
227 11000111 IC7 TH21 (intake)
228 00100111 IC8 TH21 (intake)
229 10100111 IC6 SC/SH
−99.9–999.9 (°C)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to “0” during cooling operation)
Note: Display of indoor SC/SH data
230 01100111 IC7 SC/SH
231 11100111 IC8 SC/SH
232 00010111 Target indoor SC/
SH (IC6)
SCm/SHm (0.0–20.0) (°C)
Note: Display of all control target data
233 10010111 Target indoor SC/
SH (IC7)
234 01010111 Target indoor SC/
SH (IC8)
235 11010111 IC6 LEV opening
pulse abnormality
delay
0–2000 (pulse)
Note: Display of opening pulse of indoor LEV at time of abnormality delay
236 00110111 IC7 LEV opening
pulse abnormality
delay
237 10110111 IC8 LEV opening
pulse abnormality
delay
238 01110111 IC6 SC/SH at
time of abnormali
-
ty delay
−99.9–999.9 (°C)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to “0” during cooling operation)
Note: Display of indoor SC/SH data at time of abnormality delay
239 11110111 IC7 SC/SH at
time of abnormali
-
ty delay
240 00001111 IC8 SC/SH at
time of abnormali
-
ty delay
241 10001111 IC6 LEV opening
pulse at time of
abnormality
0–2000 (pulse)
Note: Display of opening pulse of indoor LEV at time of abnormality
242 01001111 IC7 LEV opening
pulse at time of
abnormality
243 11001111 IC8 LEV opening
pulse at time of
abnormality
244 00101111 IC6 SC/SH at
time of abnormali
-
ty
−99.9–999.9 (°C)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to “0” during cooling operation)
Note: Display of indoor SC/SH data at time of abnormality delay
245 10101111 IC7 SC/SH at
time of abnormali
-
ty
246 01101111 IC8 SC/SH at
time of abnormali
-
ty
250 01011111 IC9 LEV opening
pulse
0–2000 (pulse)
Note: Display of opening pulse of indoor LEV
251 11011111 IC10 LEV opening
pulse
252 00111111 IC11 LEV opening
pulse
253 10111111 IC12 LEV opening
pulse
Содержание CITY MULTI PUMY-P200YKM3
Страница 20: ...OCH791 _20 6 OUTLINES AND DIMENSIONS Unit mm ...
Страница 21: ...OCH791 _21 7 WIRING DIAGRAM ...
Страница 103: ...OCH791 _103 Photo 16 Accumulator Inlet Outlet Photo 17 Accumulator Accumulator leg Accumulator leg fixing screws ...
Страница 106: ...OCH791 _106 11 ELECTRICAL WIRING Refer to installation manual 6 Electrical work for details ...