OCH791 _94
SW1
setting
Contents
LED1, 2
No. 12345678
1
2
3
4
5
6
7
8
141 10110001 OC SC (cooling)
at time of
abnormality delay
−99.9–999.9(°C)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to “0” during cooling operation)
Note: Display of data from high pressure sensor, all thermistors, and SC/SH at time of abnormality delay
142 01110001 IC1 SC/SH at
time of abnormali
-
ty delay
143 11110001 IC2 SC/SH at
time of abnormali
-
ty delay
144 00001001 IC3 SC/SH at
time of abnormali
-
ty delay
145 10001001 IC4 SC/SH at
time of abnormali
-
ty delay
146 01001001 IC5 SC/SH at
time of abnormali
-
ty delay
147 11001001 IC9 SC/SH at
time of abnormali
-
ty delay
148 00100001 IC10 SC/SH at
time of abnormali
-
ty delay
149 10101001 IC11 SC/SH at
time of abnormali
-
ty delay
150 01101001 IC12 SC/SH at
time of abnormali
-
ty delay
151 11101001 IC9 LEV opening
pulse at time of
abnormality
0–2000 (pulse)
Note: Display of opening pulse of indoor LEV at time of abnormality
152 00011001 IC10 LEV opening
pulse at time of
abnormality
153 10011001 IC11 LEV opening
pulse at time of
abnormality
154 01011001 IC12 LEV opening
pulse at time of
abnormality
155 11011001 IC9 SC/SH at
time of abnormali
-
ty
−99.9–999.9 (°C)
During heating: subcool (SC)
During cooling; superheat (SH) (Fixed to “0” during cooling operation)
Note: Display of indoor SC/SH data at time of abnormality
156 00111001 IC10 SC/SH at
time of abnormali
-
ty
157 10111001 IC11 SC/SH at
time of abnormali
-
ty
158 01111001 IC12 SC/SH at
time of abnormali
-
ty
159 11111001 IC9 Capacity
code
0–255
Notes:
Display of indoor unit capacity code
The No.1 unit will start from the M-NET address with the lowest number
160 00000101 IC10 Capacity
code
161 10000101 IC11 Capacity
code
162 01000101 IC12 Capacity
code
163 11000101 IC9 SC/SH
−99.9–999.9 (°C)
During heating: subcool (SC)
During cooling; superheat (SH) (Fixed to “0” during cooling operation)
Note: Display of indoor SC/SH data
164 00100101 IC10 SC/SH
165 10100101 IC11 SC/SH
166 01100101 IC12 SC/SH
170 01010101 ROM version
monitor
0.00–99.99 (ver)
Note: Display of version data of ROM
171 11010101 ROM type
Note: Display of ROM type
172 00110101 Check sum mode 0000–FFFF
Note: Display of check sum code of ROM
173 10110101 IC9 TH23 (Gas)
−99.9–999.9 (°C)
Note: Display detected data of indoor unit thermistors
174 01110101 IC10 TH23 (Gas)
175 11110101 IC11 TH23 (Gas)
176 00001101 IC12 TH23 (Gas)
177 10001101 IC9 TH22 (Liquid)
178 01001101 IC10 TH22
(Liquid)
179 11001101 IC11 TH22
(Liquid)
180 00101101 IC12 TH22
(Liquid)
185 10011101 IC9 TH21 (Intake)
186 01011101 IC10 TH21
(Intake)
187 11011101 IC11 TH21
(Intake)
188 00111101 IC12 TH21
(Intake)
Содержание CITY MULTI PUMY-P200YKM3
Страница 20: ...OCH791 _20 6 OUTLINES AND DIMENSIONS Unit mm ...
Страница 21: ...OCH791 _21 7 WIRING DIAGRAM ...
Страница 103: ...OCH791 _103 Photo 16 Accumulator Inlet Outlet Photo 17 Accumulator Accumulator leg Accumulator leg fixing screws ...
Страница 106: ...OCH791 _106 11 ELECTRICAL WIRING Refer to installation manual 6 Electrical work for details ...