OCH791 _10
3-4-3. Operating temperature range
Cooling
Heating
Indoor intake air temperature
W.B. 15 to 24°C
D.B. 15 to 27°C
Outdoor intake air temperature
D.B. −5 to 52°C
*1
W.B. −20 to 15°C
D.B.: Dry Bulb Temperature
W.B.: Wet Bulb Temperature
*1. 10 to 52°C D.B.: When connecting PKFY-P10/15/20/25/32VLM, PFFY-P20/25/32VKM, PFFY-P20/25/32VCM,
PFFY-P20/25/32VLEM, PFFY-P20/25/32VLRM(M), and M series, S series, and P series type indoor
unit.
■
When connecting fresh air type indoor unit
PEFY-P·VMHS-E-F
Cooling
Heating
Indoor and outdoor intake air temperature
D.B. 17 to 43°C
*2
W.B. 15.5 to 35°C
D.B. -10 to 20°C
*3
*2. Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is lower than 17°C D.B.
*3. Thermo-OFF (FAN-mode) automatically starts if the outdoor temp. is higher than 21°C D.B.