
OCH791 _13
5-1-2. Heating
Design condition
Outdoor wet bulb temperature
2°C
Total heating load
20.4 kW
Room 1
Indoor dry bulb temperature
21°C
Heating load
9.5 kW
Room 2
Indoor dry bulb temperature
23°C
Heating load
10.9 kW
Other
Indoor/Outdoor piping equivalent length
40 m
Capacity of indoor unit
P·FY series Model class of indoor unit 10 15
—
20
—
25
32
—
40
—
50
—
63
71
80
100 125 140 200
Model Capacity (kW)
1.4 1.9
—
2.5
—
3.2 4.0
—
5.0
—
6.3
—
8.0 9.0 10.0 12.5 16.0 18.0 25.0
M series
S series
P series
Model class of indoor unit —
15
—
20
22
25
—
35
—
42
50
60
—
71
—
100
—
—
—
Model Capacity (kW)
—
1.7
—
2.3 2.5 2.9
—
4.0
—
4.8 5.7 6.9
—
8.1
— 11.2 —
—
—
■
Heating calculation
• Tentative selection of indoor units
Room1: PEFY-P80
10.0 kW (Rated)
Room2: PEFY-P100
12.5 kW (Rated)
In this case, the total capacity is 22.5. (10.0 + 12.5 = 22.5)
• Tentative selection of outdoor unit
Proper outdoor unit in this case is P200 as the total capacity of the indoor units is 22.5.
PUMY-P200
25.0 kW
• Calculation for the corrected capacity of the total indoor units (CTi)
Correction factor for indoor temperature: Room 1 (21°C)
0.96 (Refer to Figure 3.)
Room 2 (23°C)
0.88 (Refer to Figure 3.)
CTi = Σ (Rated capacity of indoor unit × Correction factor for indoor temperature)
= 10.0 × 0.96 + 12.5 × 0.88
= 20.6 kW
• Calculation for the corrected capacity of the outdoor unit (CTo)
Correction factor for outdoor temperature (2°C WB)
1.00 (Refer to Figure 4.)
Correction factor for piping length (40 m)
0.98 (Refer to "Correcting Capacity".)
Correction factor for defrosting
0.89 (Refer to Table 1.)
CTo = Rated capacity of outdoor unit × Correction factor for outdoor temperature × Correction factor for piping length ×
Correction factor for defrosting
= 25.0 × 1.00 × 0.98 × 0.89
= 21.8 kW
Table 1 Table of correction factor for frosting and defrosting
Outdoor inlet air temp. (°C)
6
4
2
0
-2
-4
-6
-8
-10
-15
-20
Correction factor
1.00 0.98 0.89 0.88 0.89 0.90 0.95 0.95 0.95 0.95 0.95
• Determination of maximum system capacity (CTx)
Comparison between CTi and CTo:
CTi = 20.6 < CTo = 21.8, thus, select CTi.
CTx = CTi = 20.6 kW
• Comparison with essential load
Against the essential load 20.4 kW, the maximum system capacity is 20.6 kW: Proper indoor units have been select-
ed.
• Calculation for the maximum indoor unit capacity of each room
When CTx = CTi, use the calculation formula below.
Room1: Rated capacity of Indoor unit × Correction factor for indoor temperature
= 10.0 × 0.96
= 9.6 kW
The capacity is enough for the heating load of Room 1 (9.5 kW): A proper indoor unit is selected.
Room2: Rated capacity of indoor unit × Corrected capacity for the indoor design temperature
= 12.5 × 0.88
= 11.0 kW
The capacity is enough for the heating load of Room 2 (10.9 kW): A proper indoor unit is selected.
Note:
• If CTx = CTo, refer to the calculation formula in "Cooling" to calculate the maximum indoor unit capacity of each
room.
• The selection of units is completed when proper units are selected.
Содержание CITY MULTI PUMY-P200YKM3
Страница 20: ...OCH791 _20 6 OUTLINES AND DIMENSIONS Unit mm ...
Страница 21: ...OCH791 _21 7 WIRING DIAGRAM ...
Страница 103: ...OCH791 _103 Photo 16 Accumulator Inlet Outlet Photo 17 Accumulator Accumulator leg Accumulator leg fixing screws ...
Страница 106: ...OCH791 _106 11 ELECTRICAL WIRING Refer to installation manual 6 Electrical work for details ...