OCH791 _95
SW1
setting
Contents
LED1, 2
No. 12345678
1
2
3
4
5
6
7
8
189 10111101 History of voltage
error (U9/4220)
—
—
PAM error
Converter
Fault
Power
synchroniza
-
tion signal
error
L1 open
phase error
Under voltage
error
Over voltage
error
190 01111101 External connec
-
tion status at time
of abnormality
delay
CN3N 1-3
input
CN3N 1-2
input
CN3S 1-2
input
CN3D 1-3
input
CN3D 1-2
input
—
—
—
191 11111101 External connec
-
tion status at time
of abnormality
CN3N 1-3
input
CN3N 1-2
input
CN3S 1-2
input
CN3D 1-3
input
CN3D 1-2
input
—
—
—
192 00000011 Actual frequency
of abnormality
0–255 (Hz)
Note: Display of actual frequency at time of abnormality
193 10000011 Fan step number
at time of
abnormality
0–15
Note: Display of fan step number at time of abnormality
195 11000011 IC1 LEV opening
pulse at time of
abnormality
0–2000 (pulse)
Note: Display of opening pulse of indoor LEV at time of abnormality
196 00100011 IC2 LEV opening
pulse at time of
abnormality
197 10100011 IC3 LEV opening
pulse at time of
abnormality
198 01100011 IC4 LEV opening
pulse at time of
abnormality
199 11100011 IC5 LEV opening
pulse at time of
abnormality
200 00010011 High pressure
sensor data at
time of abnormali
-
ty
−99.9–999.9 (kgf/cm²)
Note: Display of data from high pressure sensor, all thermistors, and SC/SH at time of abnormality
201 10010011 TH4 (Compres
-
sor) sensor data
at time of
abnormality
−99.9–999.9 (°C)
Note: Display of data from high pressure sensor, all thermistors, and SC/SH at time of abnormality
202 01010011 TH6 (Suction
pipe) sensor data
at time of
abnormality
203 11010011 TH3 (Outdoor
liquid pipe) sensor
data at time of
abnormality
204 00110011 TH8 (Heat sink)
sensor data at
time of abnormali
-
ty
205 10110011 OC SC (cooling)
at time of
abnormality
−99.9–999.9 (°C)
During heating: subcool (SC)
During cooling: superheat (SH) (Fixed to “0” during cooling operation)
Note: Display of indoor SC/SH data at time of abnormality
206 01110011 IC1 SC/SH at
time of abnormali
-
ty
207 11110011 IC2 SC/SH at
time of abnormali
-
ty
208 00001011 IC3 SC/SH at
time of abnormali
-
ty
209 10001011 IC4 SC/SH at
time of abnormali
-
ty
210 01001011 IC5 SC/SH at
time of abnormali
-
ty
211 11001011 IC6 Capacity
code
0–255
Note:
Display of indoor unit capacity code
The No.1 unit will start from the M-NET address with the lowest number.
212 00101011 IC7 Capacity
code
213 10101011 IC8 Capacity
code
214 01101011 IC6 operation
mode
STOP
Fan
Cooling
thermo-ON
Cooling
thermo-OFF
Heating
thermo-ON
Heating
thermo-OFF
—
—
215 11101011 IC7 operation
mode
216 00011011 IC8 operation
mode
Note: Display of indoor unit operation mode
217 10011011 IC6 LEV opening
pulse
0–2000 (pulse)
Note: Display of opening pulse of indoor LEV
218 01011001 IC7 LEV opening
pulse
219 11011001 IC8 LEV opening
pulse
Содержание CITY MULTI PUMY-P200YKM3
Страница 20: ...OCH791 _20 6 OUTLINES AND DIMENSIONS Unit mm ...
Страница 21: ...OCH791 _21 7 WIRING DIAGRAM ...
Страница 103: ...OCH791 _103 Photo 16 Accumulator Inlet Outlet Photo 17 Accumulator Accumulator leg Accumulator leg fixing screws ...
Страница 106: ...OCH791 _106 11 ELECTRICAL WIRING Refer to installation manual 6 Electrical work for details ...