3 OVERVIEW OF UNITS
3-1. System construction
Wireless remote
controller
M series indoor unit
*4, *5
MSZ-SF·VA/VE series
MSZ-EF·VE/VG(K) series
MSZ-FH·VE series
MFZ-KJ·VE series
MFZ-KT·VG series
MSZ-LN·VG(2) series
MSZ-AP·VG(K) series
MSZ-AP·VF series
CONNECTION KIT
PAC-LV11M-J
Model name
CMY-Y62-G-E
CMY-Y64-G-E
CMY-Y68-G-E
Number of branches
2
4
8
Outdoor unit
Horsepower
8 HP
Model name
P200
Applicable indoor unit
Capacity class
10 to 200
Number of units
1 to 12
Total system capacity range
50 to 130% of outdoor unit capacity
*1
Connectable indoor unit lineup
Model type
Model name
10
15
20
25
32
40
50
63
71
80
100 125 140 200
Cassette
ceiling
2 by 2
PLFY-P·VFM-E1
● ● ● ● ● ●
2-way
flow
PLFY-P·VLMD-E
● ● ● ● ● ●
● ● ●
4-way
flow
PLFY-P·VBM-E
● ● ● ● ● ●
● ● ●
PLFY-P·VEM-E
● ● ● ● ● ●
● ● ●
PLFY-M·VEM6-E
● ● ● ● ● ● ● ● ● ●
PLFY-M·VEM-E
● ● ● ● ● ●
● ● ●
1-way flow
PMFY-P·VBM-E
● ● ● ●
Ceiling concealed
PEFY-P·VMS1(L)-E
● ● ● ● ● ● ●
PEFY-P·VMA(L)-E/E2
● ● ● ● ● ● ● ● ● ● ●
PEFY-P·VMA(L)-E3
● ● ● ● ● ● ● ● ● ● ●
PEFY-P·VMHS-E
● ● ● ● ● ● ● ● ●
PEFY-P·VMR-E-L/R
● ● ●
PEFY-M·VMA(L)-A1
● ● ● ● ● ● ● ● ● ● ●
Wall mounted
PKFY-P·VLM-E
● ● ● ● ● ● ●
PKFY-P·VKM-E
●
●
Ceiling suspended
PCFY-P·VKM-E
●
●
● ●
Floor
standing
Exposed
PFFY-P·VLEM-E
● ● ● ● ● ●
PFFY-P·VKM-E2
● ● ● ●
Concealed PFFY-P·VLRM(M)-E
● ● ● ● ● ●
PFFY-P·VCM-E
● ● ● ● ● ●
Ceiling
concealed
Fresh air
*2
PEFY-P·VMHS-E-F
●
Lossnay
GUF·RD(H)4
*3
●
●
Remote controller
Name
M-NET remote controller
MA remote controller
Model name
PAR-F27MEA-E, PAR-U02MEDA
PAR-4xMAA, PAR-3xMAA ("x" represents 0 or later)
Functions
• A handy remote controller for use in conjunction
with the Melans centralized management system.
• Address setting is required.
• Address setting is not required.
*1. When the indoor unit of Fresh Air type is connected with the outdoor unit, the maximum connectable total indoor unit
capacity is 110%.
*2. PUMY is connectable to Fresh Air type indoor unit.
It is possible to connect 1 Fresh Air type indoor unit to 1 outdoor unit. (1:1 system)
Operating temperature range (outdoor temperature) for fresh air type indoor units differ from other indoor units.
Refer to "3-4-3. Operating temperature range".
*3. Do not connect Lossnay remote controller(s). (PZ-61DR-E, PZ-60DR-E, PZ-52SF-E, PZ-43SMF-E)
*4. When connecting the CONNECTION KIT (PAC-LV11M-J) and an M-series indoor unit, refer to the installation manual
for the CONNECTION KIT.
*5. The CONNECTION KIT cannot be connected to the indoor unit whose model name is 60 or larger and LN 18.