OCH791 _70
7101 (EF): Capacity code error
Abnormal points and detection methods
• A connected indoor unit is incompatible, error code
7101 is displayed.
Causes and checkpoints
The model name of connected indoor unit (capacity code)
is read as incompatible.
The connectable indoor units are:
• P10 to P200 model (capacity code 2 to 40)
• When connecting via branch box:
P15 to P100 model (capacity code 4 to 20)
Diagnosis of failure
Set the switch properly.
The capacity code of the connected indoor unit
can be displayed by an operation of SW1 on the
outdoor unit.
Check the model selection switch (SW4
on the indoor controller board) of the
connected indoor unit.
Is it set properly?
Yes
No