OCH791 _93
SW1
setting
Contents
LED1, 2
No. 12345678
1
2
3
4
5
6
7
8
107 11010110 Target outdoor
SC (cooling)
SCm (0.0–20.0) (°C)
Note: Display of all control target data
108 00110110 Target indoor SC/
SH (IC1)
SCm/SHm (0.0–20.0) (°C)
Note: Display of all control target data
109 10110110 Target indoor SC/
SH (IC2)
110 01110110 Target indoor SC/
SH (IC3)
111 11110110 Target indoor SC/
SH (IC4)
112 00001110 Target indoor SC/
SH (IC5)
113 10001110 Indoor unit check
status (IC9-12)
No.9 unit
check
No.10 unit
check
No.11 unit
check
No.12 unit
check
—
—
—
—
Note: Light on at time of abnormality
114 01001110 Indoor unit
operation mode
(IC9-12)
No.9 unit
mode
No.10 unit
mode
No.11 unit
mode
No.12 unit
mode
—
—
—
—
Note: COOL/DRY: light on, HEAT: light blinking, FAN/STOP: light off
115 11001110 Indoor unit
operation display
(IC9-12)
No.9 unit
operation
No.10 unit
operation
No.11 unit
operation
No.12 unit
operation
—
—
—
—
Note: Thermo-ON: light on, Thermo-OFF: light off
116 00101110 IC9 operation
mode
STOP
Fan
Cooling
Thermo-ON
Cooling
thermo-OFF
Heating
thermo-ON
Heating
thermo-OFF
—
—
117 10101110 IC10 operation
mode
118 01101110 IC11 operation
mode
119 11101110 IC12 operation
mode
Note: Display of indoor unit operation mode
120 00011110 Target indoor SC/
SH (IC9)
SCm/SHm (0.0–20.0) (°C)
Note: Display of all control target data
121 10011110 Target indoor SC/
SH (IC10)
122 01011110 Target indoor SC/
SH (IC11)
123 11011110 Target indoor SC/
SH (IC12)
124 00111110 IC9 LEV opening
pulse abnormality
delay
0–2000 (pulse)
Note: Display of opening pulse of indoor LEV at time of abnormality delay
125 10111110 IC10 LEV opening
pulse abnormality
delay
126 01111110 IC11 LEV opening
pulse abnormality
delay
127 11111110 IC12 LEV opening
pulse abnormality
delay
128 00000001 Actual frequency
of abnormality
delay
0–255 (Hz)
Note: Display of actual frequency at time of abnormality delay
129 10110001 Fan step number
at time of
abnormality delay
0–15
Note: Display of fan step number at time of abnormality delay
131 11000001 IC1 LEV opening
pulse abnormality
delay
0–2000 (pulse)
Note: Delay of opening pulse of indoor LEV at time of abnormality delay
132 00100001 IC2 LEV opening
pulse abnormality
delay
133 10100001 IC3 LEV opening
pulse abnormality
delay
134 01100001 IC4 LEV opening
pulse abnormality
delay
135 11100001 IC5 LEV opening
pulse abnormality
delay
136 00010001 High pressure
sensor data at
time of abnormali
-
ty delay kgf/cm
2
−99.9–999.9 (kgf/cm²)
Note: Display of data from high pressure sensor, all thermistors, and SC/SH at time of abnormality delay
137 10010001 TH4 (Compres
-
sor) sensor data
at time of
abnormality delay
−99.9–999.9 (°C)
Note: Display of data from high pressure sensor, all thermistors, and SC/SH at time of abnormality delay
138 01010001 TH6 (Suction
pipe) sensor data
at time of
abnormality delay
139 11010001 TH3 (Outdoor
liquid pipe) sensor
data at time of
abnormality delay
140 00110001 TH8 (Heat sink)
sensor data at
time of abnormali
-
ty delay