OCH791 _116
Notes:
•
When the test run is completed, the ˝Test run menu˝ screen will appear.
• The test run will automatically stop after 2 hours.
• The function is available only for the model with vanes.
Remain
Vert
Horiz
i-see
Test run
F1
F2
F3
F4
Auto
Auto
Ind.
13-4-2. PAR-SL97A-E
Measure an impedance between the power supply terminal block on the outdoor unit and ground with a 500 V Megger
and check that it is equal to or greater than 1.0 MΩ.
Operating instructions
1. Turn on the main power to the unit.
2. Press the
TEST RUN
button twice continuously.
(Start this operation from the status of remote controller display turned off.)
The symbol of
TEST RUN
and current operation mode are displayed.
3. Press the
MODE
button to activate COOL mode, then check whether cool air blows out from the unit.
4. Press the
MODE
button to activate HEAT mode, then check whether warm air blows out from the unit.
5. Press the
FAN
button and check whether strong air blows out from the unit.
6. Press the
VANE
button and check whether the auto vane operates properly.
7. Press the
button to stop the test run.
Notes:
• Point the remote controller towards the indoor unit receiver to perform steps 2 to 7.
•
It is not possible to run in FAN, DRY or AUTO mode.
ON/OFF
TEMP
FAN
VANE
MODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
TEST RUN
RESET
SET
CLOCK
7
5
6
2
3, 4
13-4-3. PAR-SL101A-E
Operating instructions
1. Stop the air conditioner
• Press the
button to stop the air conditioner.
•
If the weekly timer is enabled (
is shown on the display), press the
button to disable it (
is off).
2. Start the test run
• Press the
button for 5 seconds.
CHECK
appears on the display and the unit starts the service mode.
• Press the
button.
appears on the display and the unit starts the test run mode.
• Press the following buttons to start the test run.
: Switch the operation mode between cooling and heating and start the test run.
: Switch the fan speed and start the test run.