14. Removing the compressor (MC)
1. Remove the service panel. (See Photo 1)
2. Remove the top panel. (See Photo 1)
3. Remove 2 cover panel (front) fixing screws (5 × 12) and remove the cover panel (front). (See Photo 4)
4. Remove front panel fixing screws 5 (5 × 12) and 2 (4 × 10), and remove the front panel. (See Photo 4)
5. Remove 4 cover panel (rear) fixing screws (5 × 12) and remove the cover panel (rear).
6. Remove the electrical parts box. (See Photo 5)
7. Remove 3 valve bed fixing screws (4 × 10) and 4 ball valve and stop valve fixing screws (5 × 16) and then remove
the valve bed. (See Photo 4 and 7)
8. Remove 3 side panel (R) fixing screws (5 × 12) in the rear of the unit and then remove the side panel (R).
9. Remove 3 separator fixing screws (4 × 10) and remove the separator. (See Figure 1)
10. Recover refrigerant.
11. Remove the 3 compressor fixing nuts for motor using spanner or adjustable wrench.
12. Remove the welded pipe of motor for compressor inlet and outlet and then remove the compressor.
Note:
•
Recover refrigerant without spreading it in the air.
Photo 15
Compressor
(MC)
Valve bed
Valve bed
fixing screw
Valve
bed fixing
screws
Compressor
fixing nuts
Compressor
fixing nuts
Separator
Accumulator
Figure 1
Separator
fixing screws
Separator
fixing screw
15. Removing the accumulator
1. Remove the service panel. (See Photo 1)
2. Remove the top panel. (See Photo 1)
3. Remove 2 cover panel (front) fixing screws (5 × 12) and remove the cover panel (front). (See Photo 4)
4. Remove 4 cover panel (rear) fixing screws (5 × 12) and remove the cover panel (rear).
5. Remove the electrical parts box. (See Photo 5)
6. Remove 3 side panel (R) fixing screws (5 × 12) in the rear of the unit and then remove the side panel (R).
7. Remove 3 side panel (R) fixing screws (5 × 12) in the rear of the unit and then remove the side panel (R).
8. Recover refrigerant.
9. Remove 2 welded pipes of accumulator inlet and outlet.
10. Remove 2 accumulator leg fixing screws (4 × 10).
Note:
•
Recover refrigerant without spreading it in the air.