5. SEQUENCE PROGRAMS AND SFC PROGRAMS
5
−
18
[Data Settings]
(1) Setting the axis for which a speed change is to be executed
The axis with respect to which the speed change set in (D) is to be executed is
set as follows.
Started axis No.
Only J can be used.
J
⋅
Set the relevant axis No. in the range 1 to 8 or 1 to 4
⋅
Set the interpolation control time for one of the axes involved
in the interpolation.
Axes to be started are designated as shown below.
•
Axis 1 .................. J1
(2) Setting the speed change
There are two types of setting for speed changes: direct setting and indirect
setting.
(a) In direct setting, the speed to be changed to is specified directly as a
numerical value. (For the setting range, refer to Section 3.2.2.).
If the speed to be changed "10", the setting as follows.
•
When designated with a K device................ K10
(b) The word devices that can be used are indicated in the table below.
1) The word devices that can be used are indicated in the table below.
Word Device
Usable Devices
D
0 to 799
W
0 to 3FF
R
0 to 8191
Make the following setting to designate the present value to be changed to
with the data stored in data register D50:
•
Designation with a word device
CHGV J11
D50
2) An index register (Z, V) can be used for index designation of the indirectly
set word device.
Example
Example
Example
Downloaded from