Configuration and CFG-300 LCD Service Tool
58
Remote Annunciator
Troubles related to the annunciator can have two possibilities: either the main panel and annunciator failed to
communicate with each other, or an un-configured remote annunciator is responding to the main panel. In both the
cases, the following trouble message is displayed:
Four-wire smoke detector supply
The four-wire smoke detector supply is supervised for shorts. When a short is detected on a four-wire smoke supply
the power is cut off and a trouble message is generated. Press the system “RESET” key to restore the power the
system. If the short is removed, the panel will return to normal; otherwise the trouble message will stay.
Note:
The trouble code and info is for trained service personnel only.
R A U n u m m i s m a t c h
t r o u b l e 1 / 1
T r b : 0 x 0 3 I n f o : 0 x 0 0 0 1
1 1 : 4 5 S A T 2 0 0 3 - 0 2 - 0 3
T roub le Type
E V E N T
01 of 09
D AT E
T IM E
"IN FO "
Key
Trouble code
T rouble info
"IN FO "
Key
4 W i r e P w r . S u p p l y
s h o r t 1 / 1
T roub le Type
E V E N T
01 of 01
T r b : 0 x 0 3 I n f o : 0 x 0 0 0 1
0 0 : 0 7 S A T 2 0 0 0 - 0 1 - 0 1
D AT E
T IM E
Trouble code
T rouble Info