Configuration and CFG-300 LCD Service Tool
56
11. Exit (Command-Menu)
Pressing, “ENTER” after selecting “Exit“ from the menu will return the panel to normal LCD operation.
CFG-300 LCD Service tool operation
If an LCD service tool is connected to the panel, you will only be able to view the latest message–you cannot scroll
through them. In order to see all of the messages, you must enter the programming menu and see the event logs.
The logs are arranged so that the most recent message is shown first. Listed below are the different kinds of
messages that can be displayed on the LCD service tool.
Zone messages
Point annunciation is indicated on the LCD. There are no separate queues for “TROUBLE”, “ALARM”,
“SUPERVISORY” and “MONITOR”; instead there is only one queue that indicates all the events. The respective
TROUBLE, ALARM, SUPVISORY and MONITOR LEDs will be flashing if at least one of the given types is in the
queue.
The LCD service tool will only show the first alarm or trouble. If a trouble happens first and then an alarm, the alarm
will be displayed. Any further events will change the total number of events, shown in the right hand corner of the
LCD display. The order of priority is alarm, supervisory, trouble and monitor.
Example 1 (detection circuit):
Event “
01/09
” 01 of 09, “
OPEN TRB
” on physical “
Z-01
” at “
EAST LOBBY ENTRANCE
”. Press the INFO key to
show the process type as “
VERIFIED ALARM
” and the event occurred on “
2003/04/04
” at “
18:01 TUESDAY
”.
Example 2 (indicating circuit):
Event “
02/09
” 02 of 09, “
SHORT TRB
” on physical “
NAC-01
” at “
EAST WING LOBBY
” with process type as
“
SILENCEABLE
” and the event occurred on “
2003/02/02
” at “
18:01 TUESDAY
”.
Other common messages are listed on the following pages.
E A S T L O B B Y E N T R A N C E
O P E N T R B 0 1 / 0 9
V E R I F I E D A L A R M Z - 0 1
1 8 : 0 1 T U E 2 0 0 3 - 0 4 - 0 4
ZO N E
M essage
E V E N T
01 of 09
Process
Type
Physical
Zone N o.
D AT E
T IM E
"IN FO "
Key
EV E N T
type
E A S T W I N G L O B B Y
S H O R T T R B 0 2 / 0 9
S I L E N C E - A B L E N A C - 1
1 8 : 0 1 T U E 2 0 0 3 - 0 2 - 0 2
"IN FO "
Key
ZO N E
M essage
EV E N T
type
E V E N T
02 of 09
Process
Type
Physical
Zone N o.
D AT E
T IM E