System Components
4
System Components
Main Fire Control Panel
Relay Modules: Six Relays
Polarity reversal/city tie
Model
Description
FA-300-6LD(R/W)*
6 Zone Fire Alarm Control Panel with LED
display (white door, black box). 6 Class B (Style
B) Initiating circuits, and two Power Limited
Class B (Style Y) Indicating circuits (up to 1.70
amperes each, 5 amperes total). One six zone
ICAC-306
Input
Class A Converter
adder
modules may be used for Class A (Style D)
wiring of Initiating circuits. One
OCAC-302
Output Class A Converter
adder module may
be used for Class A (Style Z) wiring of the
Indicating circuits. The FA-300-6LD contains
Common Alarm, Common Supervisory &
Common Trouble Relays, auxiliary alarm relay
(disconnectable), an RS-485 Interface for
Remote Annunciators and a Resettable Four
Wire Smoke Detector Power Supply. The unit
has a dialer on main board. Used with BA-110
(10 amp-hour) (Sota Enertech model SA12120)
batteries (two required).
FA-300-6L
Six-zone Fire Alarm with LED display. Same
as except without dialer.
*R = red door; W = white door
Model
Description
RM-306
Six-relay adder module
Model
Description
PR-300
Polarity Reversal and/or City
tie Module
NO/NC
C
RELAY 1
NO/NC
C
RELAY 2
NO/NC
C
RELAY 3
NO/NC
C
RELAY 4
C
RELAY 5
NO/NC
C
RELAY 6
NO/NC
PO
LA
RIT
Y
RE
VE
RS
AL
AL
AR
M
PO
LA
RIT
Y
RE
VE
RS
AL
SU
PV
CI
TY
TIE
+ | -
+ | -
+ | -
JW
1
JW
2
JW4