Configuration and CFG-300 LCD Service Tool
50
Command Menu/Dialer Config/Account Info
2.Account#1 Telephone Number
[101]->Default
Use this function to set the telephone number
of the monitoring station. The maximum # of
digits allowed is 19 including “,” and numerals.
The “,” will be treated as 1 sec delay. To enter
“,” press the INFO button. Press # to move the
cursor to the right or press * to move it to the
left. An example of a typical telephone # is
9,,12345678.
Command Menu/Dialer Config/Account Info
3.Account#1 Reporting Format
[X] CONTACT ID-Default
[ ] SIA 300 Baud
[ ] SIA 110 Baud
Set the reporting format that is recognized or
preferred by the monitoring station.
Command Menu/Dialer Config/Account Info
4. Account# 2 Identification
654321->Default
Same as Account#1.
Command Menu/Dialer Config/Account Info
5.Account# 2 Telephone Number
[ 101 ]->Default
Same as Account#1.
Command Menu/Dialer Config/Account Info
6.Account# 2 Reporting Format
[X] Contact ID-Default
[ ] SIA 300 Baud
[ ] SIA 110 Baud
Same as Account#1.
Account#1 Telnum:
101
A C C N T # 1 F o r m a t :
[ X ] C o n t a c t I D
ACCOUNT#2 ID:
654321
ACCOUNT#2 Telnum:
101
A C C N T # 2 F o r m a t :
[ X ] C o n t a c t I D