Configuration and CFG-300 LCD Service Tool
38
Command Menu-->Panel Config
Inp Zone
This
Inp Zone
menu is used to program the process type for the initiating circuits. Only six circuits will be shown for
models FA-300-6LD and FA-300-6L.
Command Menu/Panel Config/Features/
16. Active EOL
[X] DISABLE->Default
[ ] NO
Enable this function if using an
Active EOL. If ICAC-306 is
used, this function should be
enabled since the Class A
Converter has built in Active
EOL resistors.
Command Menu/Panel Config/Features/
17. Verify. Alarm
[X] ULC->Default
[ ] ULI
Select alarm verification timing
according to ULI or ULC
standard.
Note:
Refer to
How to Use the Keypad to Program the FA-300
on page 34 for detailed instructions on
making menu selections.
Command Menu/
Panel Config
/Ipt. Zone
1.Process Type (Initiating circuit)
6.
[X] ALARM ->Default
[ ] VERIF ALARM
[ ] SPRKL ALM
[ ] WTR-FLOW ALM
[ ] NON-LATCH SUP
[ ] LATCH SUPV
[ ] MONITOR
[ ] TRB ONLY
Use this function to program
the process type of each input
zone. (
See CIRCUIT TYPE
section for details.)
A c t i v e E O L
[ X ] D I S A B L E
A l a r m v e r i f i c a t i o n
[ X ] U L C
-Initiating Zone-
1 Zone-1
2 Zone-2
3 Zone-3
4 Zone-4
5 Zone-5
6 Zone-6
Z o n e - 1 T y p e
[ X ] A L A R M
Zone-6
[X] ALARM