DM12-01.01.05en
MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
Installation
57
5.3 Upward drainage (drain pump)
5.3.1 For Four-way cassette(compact)
5.3.2 For Four-way cassette
5.4 Convergent drainage
5.4.1
The number of indoor units should be as small as possible to prevent the traverse main pipe overlong.
5.4.2
Indoor unit with drain pump and indoor unit without drain pump should be in different drainage system.
Selection the diameter
Number of connecting indoor units
→
Calculate drainage volume
→
Select the diameter
Calculate allowed volume =Total cooling capacity of indoor units (HP) × 2 (l/ hr)
Allowed volume(lean 1/100) (l/ hr)
I.D. (mm)
Thick
Hard PVC
∽
≤
14
25
3.0
Hard PVC
14
<
∽
≤
88
30
3.5
Hard PVC
88
<
∽
≤
334
40
4.0
Hard PVC
175
<
∽
≤
334
50
4.5
Hard PVC
334
<
∽
80
6.0