MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
DM12-01.01.05en
36
Outdoor
units
5) E5 malfunction
LED indicates E5
Outdoor unit voltage protection
Check the voltage of outdoor unit power supply, whether the
voltage between L1 and N is about 198--252V
No
Replace the filter board, then check whether the system can
run normally
Check the power supply
Yes
Replace outdoor main board
Yes
Trouble is solved
No