MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
Installation
55
4.3 Refrigerant Amount to be added
Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor
unit/indoor unit connection.
Table 6-8
Liquid Side Piping
Diameter
Refrigerant to be added
Per meter Piping
6.4
0.022kg
9.5
0.060kg
12.7
0.110kg
15.9
0.190kg
19.1
0.290kg
22.2
0.380kg
NOTE
:
Additional refrigerant volume of branch pipe is 0.1kg per item (Consider the liquid side of branch pipe only)