DM12-01.01.05en
MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
Installation
63
7.2 Indoor Unit Wiring
Power Supply
Table 7-2
Capacity (Btu/h)
36000~60000
indoor Unit power
Phase
1- phase
Frequency and Voltage
220-240V~ 50Hz
Power Wiring(mm
2
)
3-core×1.0
Circuit Breaker/Fuse (A)
15/15
Indoor unit/Outdoor unit Signal wire (Weak electric signal) (mm
2
)
3-core shielded wire 3X0.5
1.
Signal wire is 3-core, polarized wire. Use 3-core shield wire to prevent interference. The grounding method
now is grounding the closed end of the shield wire and opening (insulating) at the end. Shield is to be
grounded.
2.
The control between outdoor unit and indoor unit is BUS type. An address is set on field during the
installation.
CAUTION
The wire diameter and continuous length is under the condition that the voltage vibration is within 2%. If the continuous length is
exceed showing value, choose the wire diameter follow relevant regulation.
Indoor unit power supply wiring
Fig.7-3
CAUTION
1.
Refrigerant piping system, indoor unit-indoor unit connection signal wires and indoor unit-outdoor unit connection signal wire
are in the same system.
2.
When power cord is parallel with signal wire, please put them into separate wire distribution pipes, and leave a proper distance.
(Reference distance: It is 300mm when current capacity of power cord is less than 10A, or 500mm when 50A).
Please use shield wire as indoor unit/outdoor unit signal wire.
Содержание MIV V4+ Mini
Страница 1: ...DM12 01 01 05en Service manual MIV V4 Mini DC INVERTER R410A 220V 50Hz 1Ph MVUH80A VA1 ...
Страница 2: ...Contents Part 1 General Information 1 Part 2 Outdoor Units 6 Part 3 Installation 44 ...
Страница 13: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 11 5 Wiring Diagrams MVUH80A VA1 ...
Страница 14: ...MIV V4 Mini DC Inverter R410A 220V 8 kW DM12 01 01 05en 12 Outdoor units 6 Field Wiring MVUH80A VA1 ...
Страница 23: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 21 10 Operation Limits ...