MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
DM12-01.01.05en
56
Installation
5. Processing & Installation of Drainage Pipe
5.1 Gradients and Supporting
5.1.1
Keep the drainpipe sloping downwards at a gradient of at least 1/100. Keep the drainpipe as short as
possible and eliminate the air bubble.
5.1.2
The horizontal drainpipe should be short. When the pipe is too long, a prop stand must be installed to
keep the gradient of 1/100 and prevent bending. Refer to the following table for the specification of the
prop stand.
Diameter
Distance between the prop stands
Hard PVC pipe
25~40mm
1.5~2m
Precautions
The diameter of drainpipe should meet the drainage requirement at least.
The drainpipe should be heat-insulated to prevent atomization.
Drainpipe should be installed before installing indoor unit. After powering on, there is some water in
water-receiver plate. Please check if the drain pump can act correctly.
All connection should be firm.
Wipe color on PVC pipe to note connection.
Climbing, horizontal and bending conditions are prohibited.
The dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe.
Heat-insulation should be done well to prevent condensation.
Indoor units with different drainage type can’t share one convergent drainpipe.
5.2 Drainpipe Trap
5.2.1
If the pressure at the connection of the drainpipe is negative, it needs to design drainpipe trap.
5.2.2
Every indoor unit needs one drainpipe trap.
5.2.3
A plug should be designed to do cleaning.
Plug
5
0
cm
5
0
c
m
Plug
50cm
50cm
Содержание MIV V4+ Mini
Страница 1: ...DM12 01 01 05en Service manual MIV V4 Mini DC INVERTER R410A 220V 50Hz 1Ph MVUH80A VA1 ...
Страница 2: ...Contents Part 1 General Information 1 Part 2 Outdoor Units 6 Part 3 Installation 44 ...
Страница 13: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 11 5 Wiring Diagrams MVUH80A VA1 ...
Страница 14: ...MIV V4 Mini DC Inverter R410A 220V 8 kW DM12 01 01 05en 12 Outdoor units 6 Field Wiring MVUH80A VA1 ...
Страница 23: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 21 10 Operation Limits ...