DM12-01.01.05en
MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
Installation
53
4.2 Pipe size selection
4.2.1 Selection of the refrigerant pipe
Type of the pipe
Connecting part
No.
Main pipe
Between outdoor branch joint and first branch joint
1
Indoor main pipe
Between indoor branch joint
2
Indoor pipe
Between branch part and indoor unit
3
A
4.2.2 How to choose the Branch part and the refrigerant pipe?
According the total capacity of outdoor units to select the dimension of main pipe 1:
Refrigerant
Capacity of outdoor
unit (kW)
Gas side
Liquid side
R410A
80
15.9
9.5
Remarks
A converter pipe is needed for the connection between first branch joint and outdoor unit.
Notes:
Branch header must be connected with indoor units directly, the further branch connection is not allowed.
4.2.3 The maximum connection of indoor units:
Capacity of outdoor unit (kW)
Maximum Quantity of Indoor unit
Sum capacity of indoor unit (kW)
8.0 4 2.2~10
4.2.4 According the capacity of indoor units to select indoor main pipe 2
, m
ain pipe 1 and branch joint:
Indoor main pipe dimension
The total capacity of indoor units A
Gas Side(mm)
Liquid Side(mm)
The model of branch
joint for indoor units
A≤
16.6kW
19.1
9.5
FQZHN-01
16.6
≤A≤230
22.2
9.5
FQZHN-02
Содержание MIV V4+ Mini
Страница 1: ...DM12 01 01 05en Service manual MIV V4 Mini DC INVERTER R410A 220V 50Hz 1Ph MVUH80A VA1 ...
Страница 2: ...Contents Part 1 General Information 1 Part 2 Outdoor Units 6 Part 3 Installation 44 ...
Страница 13: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 11 5 Wiring Diagrams MVUH80A VA1 ...
Страница 14: ...MIV V4 Mini DC Inverter R410A 220V 8 kW DM12 01 01 05en 12 Outdoor units 6 Field Wiring MVUH80A VA1 ...
Страница 23: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 21 10 Operation Limits ...