MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
DM12-01.01.05en
22
Outdoor
units
11. Troubleshooting
11.1 Troubles and causes of air conditioner
If one of the following malfunctions occur, stop operation, shut off the power, and contact with your
dealer.
■
The operation lamp is flashing rapidly (twice every second) This lamp is still flashing rapidly after turn off the
power and turn on again.
■
Remote controller receives malfunction or the button does not work well.
■
A safety device such as a fuse, a breaker frequently actuates.
■
Obstacles and water enter the unit.
■
Water leaks from indoor unit.
■
Other malfunctions.
If the system does not properly operate except the above mentioned cases or the above mentioned
malfunctions is evident, investigate the system according to the following procedures.
Symptoms Causes
Solution
Unit does not start
Power failure.
Power switch is off.
Fuse of power switch may have burned.
Batteries of remote controller exhausted
or other problem of controller.
Wait for the comeback of power..
Switch on the power.
Relocation.
Replace the batteries or check the
controller.
Air flowing normally but
completely can
it cooling
Temperature is not set correctly.
Be in 3 minutes protection of compressor
Set the temperature properly.
Wait.
Units start or stop
frequently
Refrigerant is too little or too much.
Air or no concreting gas in the refrigerating
circuit.
Compressor is malfunction.
Voltage is too high or too low.
System circuit is blocked.
Check leakage, and rightly recharge
refrigerant.
Vacuum and recharge refrigerant.
Maintenance or change compressor.
Install manostat.
Find reasons and solution.
Low cooling effect
Outdoor unit and indoor unit heat exchanger
is dirty.
The air filter is dirty.
Inlet/outlet of indoor/outdoor units is
blocked.
Doors and windows are open.
Sunlight directly shine.
Too much heat resource.
Outdoor temp. is too high.
Leakage of refrigerant or lack of refrigerant.
Clean the heat exchanger.
Clean the air filter.
Eliminate all dirties and make air smooth.
Close doors and windows.
Make curtains in order to shelter from
sunshine.
Reduce heat source.
AC cooling capacity reduces normal).
Check leakage and rightly recharge
Refrigerant.
Low heating effect
Outdoor temperature is lower than 7 C
Doors and windows not completely closed.
Leakage of refrigerant or lack of refrigerant.
Use heating device.
Close doors and windows.
Check leakage and rightly recharge
refrigerant.
Содержание MIV V4+ Mini
Страница 1: ...DM12 01 01 05en Service manual MIV V4 Mini DC INVERTER R410A 220V 50Hz 1Ph MVUH80A VA1 ...
Страница 2: ...Contents Part 1 General Information 1 Part 2 Outdoor Units 6 Part 3 Installation 44 ...
Страница 13: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 11 5 Wiring Diagrams MVUH80A VA1 ...
Страница 14: ...MIV V4 Mini DC Inverter R410A 220V 8 kW DM12 01 01 05en 12 Outdoor units 6 Field Wiring MVUH80A VA1 ...
Страница 23: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 21 10 Operation Limits ...