2) E2 malfunction
LED indicates E2
Communication malfunction between indoor/outdoor units
Judge 3: Check whether the signal wiring between
the indoor and outdoor units is wrong polarity?
Connect the signal wiring correctly
Yes
No
Judge 4: Check whether the signal wiring between
the indoor and outdoor units is broken?
Yes
Replace the broken wiring
No
Judge 2: Check whether the signal wiring is shield
cable or whether the shield cable is grounded
Yes
Adopt the shield cable/ shield cable
grounded
No
Indoor or outdoor main board is broken, replace the
main board until the malfunction is disappear
Judge 1: Check whether the indoor unit power is on
Turn on the indoor unit power
No
Yes