MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
DM12-01.01.05en
42
Outdoor
units
11) P5 malfunction
When condenser high temp. is more than 65°C, the unit will stop, and unit runs again when outdoor pipe temp.
less than 52°C.
LED indicates P5
Condenser high temperature protection
Check whether the condenser temperature is more than 65°C
No
Check whether the resistance of condenser
temp. sensor is correct refer to the Annex 1
Yes
Replace outdoor PCB
No
Replace the temperature sensor
Yes
Judge1: The outdoor temp. is too high(more than 43 )
Replace outdoor PCB
No
Judge 2: Check whether the heat exchanger is dirty
No
Judge 3: The refrigerant pipe is blocked
Clean the heat exchanger
Yes
Yes
Drop refrigerant, then use the high pressure
nitrogen or refrigerant to blow pipe,
vacuumize and add the refrigerant again
Yes
Stop the unit
No