DM12-01.01.05en
MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
Installation
59
6. Insulation Work
6.1 Insulation material and thickness
6.1.1
Insulation material
Insulation material should adopt the material, which is able to endure the pipe’s temperature: no less
than 70
℃
in the high-pressure side, no less than 120
℃
in the low-pressure side (For the cooling type
machine, no requirements at the low-pressure side.)
Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120
℃
)
Cooling only type---- Polyethylene foam (withstand above 100
℃
)
Thickness choice for insulation material
Insulation material thickness is as follows:
Pipe diameter (mm)
Adiabatic material thickness
Refrigerant pipe
6.4—
25.4
10mm
28.6—
38.0
15mm
38.0—
67.0
20mm
Drainage pipe
Inner diameter
20—
32
6mm
6.2 Refrigerant pipe insulation
6.2.1
Work Procedure
Before laying the pipes, the non-jointing parts and non-connection parts should be heat insulated.
After the gas proof test is eligible, the jointing area, expanding area and the flange area should be heat
insulated
Insulation for non-jointing parts and non-connection parts
Wrong Right
Gas pipe and liquid pipe should not be put
together to insulate
Insulate the gas pipe
(Cooling only)
Insulate the gas pipe and
the liquid pipe
For construction convenience, before laying pipes, use insulation material to insulate the pipes to be deal with,
at the same time, at two tips of the pipe, remain some length not to be insulated, in order to be welded and
check the leakage after laying the pipes.
Содержание MIV V4+ Mini
Страница 1: ...DM12 01 01 05en Service manual MIV V4 Mini DC INVERTER R410A 220V 50Hz 1Ph MVUH80A VA1 ...
Страница 2: ...Contents Part 1 General Information 1 Part 2 Outdoor Units 6 Part 3 Installation 44 ...
Страница 13: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 11 5 Wiring Diagrams MVUH80A VA1 ...
Страница 14: ...MIV V4 Mini DC Inverter R410A 220V 8 kW DM12 01 01 05en 12 Outdoor units 6 Field Wiring MVUH80A VA1 ...
Страница 23: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 21 10 Operation Limits ...