MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
DM12-01.01.05en
52
Installation
4. Installation of Refrigerant Pipe
CAUTION
To prevent the refrigerant piping from oxidizing inside when welding, it is necessary to charge nitrogen, or oxide will chock the
circulation system.
4.1 Length and Drop Height Permitted of the Refrigerant piping
Permitted
value
Piping
Pipe Length
Total Pipe Length (Actual)
≤
100m
L1+L2+L3+L4+L5+L6
+A+B+C+D+E
Maximum Piping(L)
Actual Length
≤
45m L1+L2+L3+L4+L5+L6+E
Equivalent Length
≤
50m L3+L4+L5+L6+E
Pipe length (from the first line branch to farthest indoor unit)
≤
20m /
Drop Height
Indoor Unit outdoor unit
Drop Height
Outdoor Unit Up
20m
/
Outdoor Unit Down
20m
/
Indoor Unit to Indoor Unit Drop Height
8m
/
Note:
Conversion of the equivalent length: Convert into the direct pipe length according to branch Junction 0.5m/l