MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
DM12-01.01.05en
24
Outdoor
units
11.3 Malfunction Code of Indoor unit
(1) For the Four-way Cassette:
No. Malfunction Operation
Timer DEF/FAN Alarm Code
1
Communication malfunction between in-outdoor unit
LED2
Quick-flash
E1
2
Room temperature sensor malfunction
LED1
Quick-flash
E2
3
Pipe temperature sensor malfunction
LED1
Quick-flash
E3
4
Pipe temperature sensor malfunction
LED1
Quick-flash
E4
5
Water level checking malfunction
LED4
Quick-flash
EE
6 EEPROM
malfunction
LED1
Slow-flash
E7
7
Mode conflicts malfunction
LED3
Quick-flash
E0
8
Outdoor
malfunction
LED4
Slow-flash
Ed
(2) For the Wall-mounted:
No. Malfunction
Code
1
Communication malfunction between in-outdoor unit
E1
2
T1 Temp. sensor malfunction
E2
3
T2A Temp. sensor malfunction
E3
4
T2B Temp. sensor malfunction
E4
5
Outdoor Unit’s (T3 or T4 or digital scroll compressor discharge) Temp. sensor malfunction
E5
6 Mode-confliction
malfunction
E6
7
Phase sequence error or Lack of phase
E0
8
Water level checking malfunction
EE
Содержание MIV V4+ Mini
Страница 1: ...DM12 01 01 05en Service manual MIV V4 Mini DC INVERTER R410A 220V 50Hz 1Ph MVUH80A VA1 ...
Страница 2: ...Contents Part 1 General Information 1 Part 2 Outdoor Units 6 Part 3 Installation 44 ...
Страница 13: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 11 5 Wiring Diagrams MVUH80A VA1 ...
Страница 14: ...MIV V4 Mini DC Inverter R410A 220V 8 kW DM12 01 01 05en 12 Outdoor units 6 Field Wiring MVUH80A VA1 ...
Страница 23: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 21 10 Operation Limits ...