![Midea MIV V4+ Mini Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/midea/miv-v4-mini/miv-v4-mini_service-manual_1790806039.webp)
DM12-01.01.05en
MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
Outdoor units
37
6) E6 malfunction
LED indicates E6
PFC module protection
Check whether the connecting line between
main board and the PFC module is
connected tightly
No
Connect it tightly, check normal or
not
Check whether the voltage between P
and N of IPM module is 270-380V
Replace the outdoor main board
Replace the PFC module