The user can press
UP
and
DOWN
cursor key to scroll through all the analog devices on the
loop. If there are no analog devices on the loop the following message will be displayed.
4. Verify counts
The verification count report displays the number of times that the alarm verification cycle has
been initiated without causing an alarm for all verified device or circuits on the specified loop or
loops. If the count is zero, the device is not displayed.
If the panel is connected to a printer, select an output source:
Select all loops or a specific loop.
Enter the loop number of the desired device and press the
Enter
button.
The report shows the loop#, device address and verify count in the following format:
The user can press
UP
and
DOWN
cursor key to scroll through all the devices on the loop for
which the verify count is available. If there are no verified devices on the loop the following
message will be displayed.
If no verified devices with a non-zero counter are found on the specified loop(s), a message is
displayed to that effect.
Verification counters are cleared by the clear verification count command and at initial power-
up.
5. Maintenance report
The maintenance report displays all smoke sensors on the specified loop or loops detected as
dirty (% alarm > 75). The percent of alarm rises as the detector gets dirty. A trouble occurs
once the percentage reaches 75%. The report shows the device address, percentage dirty,
device type, and programmed message in the following format:
No analog devices
found
- Report To -
1. Printer
2. Screen
1 All
2 Loop
Loop Number
Loop :__
Lp:1 Addr :001
Verify count :000
No verified devices
found