FX-3500 Fire Alarm Control Panel
Table 21 lists specifications for the FX-3500 panel:
Table 21 FX-3500 Specifications
FX-3500 Series Fire Alarm Control Panel
General
Digital signal processor based design, fully configurable from front panel with
password protection
Electrical ratings
AC line voltage
120VAC 60Hz/240VAC 50Hz, 10A slow blow fuse on
secondary of transformer
Power supply
rating
29VAC 10A maximum (secondary of transformer)
120VAC 60Hz 3.1Amp (maximum primary of transformer)
240VAC 50Hz 1.57Amp (maximum primary of transformer)
Total load not to exceed 10A at 24VDC
Battery
Type
24VDC Gel Cell/Sealed lead acid – 10Ah to 42Ah
Charging capability
10Ah to 42Ah
Charging current
3A maximum
Protection
20A slow blow micro fuse built into WX-058 battery cable,
field replaceable
Standby current
rating at full load
1.25A
Addressable loops
Advanced Protocol mode with one or three loops with 159 addressable sensors
and 159 addressable modules per loop. CLIP mode with one or three loops with 99
addressable sensors and 99 addressable modules per loop. The maximum loop
resistance is 40 ohms. For a complete list of compatible devices see LT-1023 on
http://www.mircom.com
.
Power Limited
/
24VDC / 350mA alarm maximum / 0.5
μ
F
Power Limited / 24VDC / 280mA normal standby maximum / 0.5
μ
F
NAC Circuits
4 supervised Class B (Style Y) or Class A (Style Z) NAC circuits, configured as
strobes or audibles. Terminals are labelled as “NAC 1”, “NAC 2”, “NAC 3” and
“NAC 4”.
Rating
Power limited / Regulated 24V FWR / 1.5A @ 49C per
circuit
Max. power allowed
Total 6.0A
1.5A per circuit
Aux supply 1
Power limited / 24VDC regulated / 500mA max.
Aux supply 2
Power limited / 24VDC regulated / 300mA max.