Battery Capacity Requirement
Battery (Ah) = (Standby Current Total x Discharge Time) + (Alarm Current Total x Alarm Time)
([STANDBY (A) ______ ] X [(24 Hours) ___ ]) + ([ALARM (B) ______ ] X [Alarm in Hr.] _____) = (C) ______Ah
Total Alarm Current must be
10
amperes or less. NAC Circuits must not exceed
6
amperes.
Battery Selection
Battery Size = Multiply (
C
) by 1.20 to derate battery.
See the following table for the recommended Mircom batteries for use with this panel.
BA-110 (12Ah) and BA-117 (18Ah) will fit into the BBX-1024DS.
To house BA-124 (26Ah) and BA-140 (42Ah) batteries a BC-160 Battery Cabinet is required.
Use of alternative batteries may result in failure of the panel to meet agency and regulatory requirements, and
may result in shortened battery life. Batteries should be tested regularly, and replaced at least every three
years. If the Battery Trouble indicator activates, obtain required service.
MIX-M500RAP(A)
Advanced Protocol Relay
Control Module (ULC)
X
0.0003
=
0.0051
=
MIX-M500SAP(A)
Advanced Protocol
Supervised Control Module
(ULC)
X
0.0004
=
0.0052
=
MIX-M501DMAP(A)
Advanced Protocol Dual
Input Mini Monitor Module
(ULC)
X
=
=
MIX-M501MAP(A)
Advanced Protocol Mini
Monitor Module (ULC)
X
0.0004
=
0.0020
=
MIX-M502MAP(A)
Advanced Protocol
Conventional Zone Module
(ULC)
X
0.0004
=
0.0052
=
B501BH(A)
Intelligent Sounder Base
(ULC)
X
0.001
=
0.015
=
B501BHT(A)
Intelligent Temporal Tone
Sounder Base (ULC)
X
0.001
=
0.015
=
APB200(-LF)
APB200(CO)A
Sounder Base (ULC)
X
0.01
=
0.140
=
INX-10A
Main Chassis (10 Amp)
X
0.0045
=
0.0045
=
Device & Remote LEDs (Maximum 20 per loop)
X
=
Signal Load (bells, horns, strobes, and etc.)
X
=
Auxiliary Power Supply (Aux 1, Aux 2, Un-filtered)
=
Alarm
=
Total currents (Add above currents)
STANDBY
(
A
)
(
B
)
Table 23 Recommended Batteries
Battery Model
Battery Size
UL/ULC Rating
BA-110
12Ah
10Ah
BA-117
18Ah
17Ah
BA-124
26Ah
24Ah
BA-140
42Ah
40Ah