93
11.2
FX-3500 System Module and Annunciator Specifications
Unfiltered supply
Power limited / 24V FWR special application / 1.7A max. at 49C
The voltage range for this output is 18.6 VDC - 36.4 VDC.
List of Compatible Devices: RAM-1016TZDS, RAM-1032TZDS(-CC), RAM-3500-
LCD, RAX-LCD-LITE
Do not use this output to power sounder bases or CZ-6, MIX-M502M, MIX-
M502MA, MIX-M502MAP, MIX-M502MAPA devices.
Auxiliary relays
Common Alarm/
Supv./Trouble/
Auxiliary Alarm
Must be connected to a listed power limited source of
supply Form C/28VDC/1A max.
RS-485 port
For remote annunciators. Terminals are labelled “RS-485”.
Ground Fault
Impedance
10 kilohms or less
Open Circuit Fault
100 kilohms or more
Short Circuit Fault
0.1 ohms or less
Applicable
Standards
NFPA 70, 72, 12, 12A, 12B, 13,15, 16, 2001, CAN/ULC-S559-13, UL-864 Rev. 10,
ULC S524, CAN/ULC-S527-11 and ULC-S536
Table 22 FX-3500 System Modules and Annunciator Specifications
FX-3500 System Modules and Annunciators
RAM-
3500LCD
Remote Annunciator
Standby 70mA / alarm 100mA
RAX-LCD-
LITE
Remote Annunciator
Standby 65mA / alarm 80mA
RTI-1
Remote Trouble Indicator
Normal standby 0mA / alarm 30mA maximum
PR-300
Polarity Reversal and City Tie Module
City Tie
power limited / 24VDC unfiltered / 270mA max. / 13.7 and
14.4 ohms
Polarity Reversal
power limited / 24VDC open / 12VDC at 3.5mA / 8mA
max. (shorted)
Polarity Reversal Supv.
Terminal
24VDC (normal) /
í
24VDC (supervisory) / 0V (trouble)
Polarity Reversal Alarm
Terminal
24VDC (normal) /
í
24VDC (alarm) / 0V (trouble)
Current Consumption
standby 50mA / alarm 300mA (city tie in use) / alarm
70mA (city tie not in use)
IPS-2424DS
Programmable Input Switches
Module with 24 switches
standby 5mA / alarm 22mA
IPS-4848DS
Programmable Input Switches
Module with 48 switches
standby 10mA / alarm 22mA
Table 21 FX-3500 Specifications (Continued)
FX-3500 Series Fire Alarm Control Panel